| Integer | nFanRet | | Number of return fans |
| Integer | nFanRel | | Number of relief fans |
| Buildings.Templates.AirHandlersFans.Components.Data.OutdoorReliefReturnSection | dat | | Design and operating parameters |
| Modelica.Units.SI.MassFlowRate | mAirSup_flow_nominal | dat.damOut.m_flow_nominal | Supply air mass flow rate |
| Modelica.Units.SI.MassFlowRate | mAirRet_flow_nominal | dat.damRet.m_flow_nominal | Return air mass flow rate |
| Modelica.Units.SI.MassFlowRate | mOutMin_flow_nominal | dat.mOutMin_flow_nominal | Minimum outdoor air mass flow rate at design conditions |
| Modelica.Units.SI.PressureDifference | dpDamOut_nominal | dat.damOut.dp_nominal | Outdoor air damper pressure drop |
| Modelica.Units.SI.PressureDifference | dpDamOutMin_nominal | dat.damOutMin.dp_nominal | Minimum outdoor air damper pressure drop |
| Modelica.Units.SI.PressureDifference | dpDamRel_nominal | dat.damRel.dp_nominal | Relief air damper pressure drop |
| Modelica.Units.SI.PressureDifference | dpDamRet_nominal | dat.damRet.dp_nominal | Return air damper pressure drop |
| Configuration |
| Buildings.Templates.AirHandlersFans.Types.OutdoorReliefReturnSection | typ | | Outdoor/relief/return air section type |
| Buildings.Controls.OBC.ASHRAE.G36.Types.OutdoorAirSection | typSecOut | | Outdoor air section type |
| Buildings.Templates.AirHandlersFans.Types.ReliefReturnSection | typSecRel | | Relief/return air section type |
| Buildings.Templates.Components.Types.Damper | typDamOut | | Outdoor air damper type |
| Buildings.Templates.Components.Types.Damper | typDamOutMin | | Minimum outdoor air damper type |
| Buildings.Templates.Components.Types.Damper | typDamRel | | Relief damper type |
| Buildings.Templates.Components.Types.Damper | typDamRet | | Return damper type |
| Buildings.Templates.Components.Types.Fan | typFanRel | | Relief fan type |
| Buildings.Templates.Components.Types.Fan | typFanRet | | Return fan type |
| Boolean | have_eco | | Set to true in case of economizer function |
| Boolean | have_recHea | false | Set to true in case of heat recovery |
| Buildings.Templates.AirHandlersFans.Types.ControlFanReturn | typCtlFanRet | Buildings.Templates.AirHandlersFans.Types.ControlFanReturn.AirflowMeasured | Return fan control type |
| Buildings.Controls.OBC.ASHRAE.G36.Types.ControlEconomizer | typCtlEco | Buildings.Controls.OBC.ASHRAE.G36.Types.ControlEconomizer.FixedDryBulb | Economizer control type |
| Dynamics › Conservation equations |
| Modelica.Fluid.Types.Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamics.DynamicFreeInitial | Type of energy balance: dynamic (3 initialization options) or steady state |
| Assumptions |
| Boolean | allowFlowReversal | true | = false to simplify equations, assuming, but not enforcing, no flow reversal |