modelDedicatedDampersPressure

Separate dampers for ventilation and economizer, with differential pressure sensor

Extends from Buildings.Templates.AirHandlersFans.Components.Interfaces.PartialOutdoorSectionDedicatedDampers (Base class for modeling separate dampers for ventilation and economizer).

Information

This model represents a configuration with an air economizer and minimum OA control with a separate minimum OA damper and differential pressure control.

Parameters

TypeNameDefaultDescription
Booleanhave_recHea (from PartialOutdoorSection)Set to true in case of heat recovery
Buildings.Controls.OBC.ASHRAE.G36.Types.ControlEconomizertypCtlEco (from PartialOutdoorSection)Economizer control type
Buildings.Templates.AirHandlersFans.Components.Data.OutdoorReliefReturnSectiondat (from PartialOutdoorSection)Design and operating parameters
Modelica.Units.SI.MassFlowRatem_flow_nominal (from PartialOutdoorSection)dat.damOut.m_flow_nominalAir mass flow rate
Modelica.Units.SI.MassFlowRatemOutMin_flow_nominal (from PartialOutdoorSection)dat.mOutMin_flow_nominalMinimum outdoor air mass flow rate
Configuration
Buildings.Controls.OBC.ASHRAE.G36.Types.OutdoorAirSectiontyp (from PartialOutdoorSection)Outdoor air section type
Buildings.Templates.Components.Types.DampertypDamOut (from PartialOutdoorSection)if typ == Buildings.Controls.OBC.ASHRAE.G36.Types.OutdoorAirSection.SingleDamper or typ == Buildings.Controls.OBC.ASHRAE.G36.Types.OutdoorAirSection.DedicatedDampersAirflow or typ == Buildings.Controls.OBC.ASHRAE.G36.Types.OutdoorAirSection.DedicatedDampersPressure then Buildings.Templates.Components.Types.Damper.Modulating else Buildings.Templates.Components.Types.Damper.NoneOutdoor air damper type
Buildings.Templates.Components.Types.DampertypDamOutMin (from PartialOutdoorSection)if typ == Buildings.Controls.OBC.ASHRAE.G36.Types.OutdoorAirSection.SingleDamper then Buildings.Templates.Components.Types.Damper.None elseif typ == Buildings.Controls.OBC.ASHRAE.G36.Types.OutdoorAirSection.DedicatedDampersAirflow then Buildings.Templates.Components.Types.Damper.Modulating elseif typ == Buildings.Controls.OBC.ASHRAE.G36.Types.OutdoorAirSection.DedicatedDampersPressure then Buildings.Templates.Components.Types.Damper.TwoPosition else Buildings.Templates.Components.Types.Damper.NoneMinimum outdoor air damper type
Dynamics › Conservation equations
Modelica.Fluid.Types.DynamicsenergyDynamics (from PartialOutdoorSection)Modelica.Fluid.Types.Dynamics.DynamicFreeInitialType of energy balance: dynamic (3 initialization options) or steady state
Assumptions
BooleanallowFlowReversal (from PartialOutdoorSection)true= false to simplify equations, assuming, but not enforcing, no flow reversal

Connectors

TypeNameDefaultDescription
Modelica.Fluid.Interfaces.FluidPort_aport_a (from PartialOutdoorSection)Fluid connector a (positive design flow direction is from port_a to port_b)
Modelica.Fluid.Interfaces.FluidPort_bport_b (from PartialOutdoorSection)Fluid connector b (positive design flow direction is from port_a to port_b)
Modelica.Fluid.Interfaces.FluidPort_aport_aHeaRec (from PartialOutdoorSection)Optional fluid connector for heat recovery
Modelica.Fluid.Interfaces.FluidPort_bport_bHeaRec (from PartialOutdoorSection)Optional fluid connector for heat recovery
Buildings.Templates.AirHandlersFans.Interfaces.Busbus (from PartialOutdoorSection)Control bus

Components

TypeNameDefaultDescription
Buildings.Templates.Components.Actuators.DamperdamOut (from PartialOutdoorSectionDedicatedDampers)Economizer outdoor air damper
Buildings.Templates.Components.Actuators.DamperdamOutMin (from PartialOutdoorSectionDedicatedDampers)Minimum outdoor air damper
Buildings.Templates.Components.Sensors.TemperatureTOut (from PartialOutdoorSectionDedicatedDampers)Outdoor air temperature sensor
Buildings.Templates.Components.Sensors.VolumeFlowRateVOutMin_flow (from PartialOutdoorSectionDedicatedDampers)Minimum outdoor air volume flow rate sensor
Buildings.Templates.Components.Sensors.SpecificEnthalpyhAirOut (from PartialOutdoorSectionDedicatedDampers)Outdoor air enthalpy sensor
Buildings.Templates.Components.Sensors.DifferentialPressuredpAirOutMin (from PartialOutdoorSectionDedicatedDampers)Minimum outdoor air damper differential pressure sensor
Buildings.Fluid.FixedResistances.JunctionjunInl (from PartialOutdoorSectionDedicatedDampers)Inlet fluid junction
Fluid.FixedResistances.JunctionjunOut (from PartialOutdoorSectionDedicatedDampers)Outlet fluid junction