blockTemSup_control
Information
General
Controller that generates temperature set-point according to outside temperature measurement. The output linearly interpolates between the minimum temperature TemSup_min, reached at maximum outside temperature TemOut_max, and the maximum temperature, reached at the minimum outside temperature TemOut_min. The controller can be used to set the supply temperature set-point at a substation or at a supply unit with respect to the current outside temperature (and thus, current heat demand).
Parameters
| Type | Name | Default | Description |
| Modelica.SIunits.Temperature | TemOut_min | -5.0 + 273.15 | Outside temperature where maximum supply temperature is used |
| Modelica.SIunits.Temperature | TemOut_max | 15.0 + 273.15 | Outside temperature where minimum supply temperature is used |
| Modelica.SIunits.Temperature | TemSup_min | 60.0 + 273.15 | Minimum supply temperature |
| Modelica.SIunits.Temperature | TemSup_max | 80.0 + 273.15 | Maximum supply temperature |
Revisions
- Feburary 27, 2019, by Benedikt Leitner:
Implementation and added User's guide.