blockTemSup_control

Information

General

Controller that generates temperature set-point according to outside temperature measurement. The output linearly interpolates between the minimum temperature TemSup_min, reached at maximum outside temperature TemOut_max, and the maximum temperature, reached at the minimum outside temperature TemOut_min. The controller can be used to set the supply temperature set-point at a substation or at a supply unit with respect to the current outside temperature (and thus, current heat demand).

Parameters

TypeNameDefaultDescription
Modelica.SIunits.TemperatureTemOut_min-5.0 + 273.15Outside temperature where maximum supply temperature is used
Modelica.SIunits.TemperatureTemOut_max15.0 + 273.15Outside temperature where minimum supply temperature is used
Modelica.SIunits.TemperatureTemSup_min60.0 + 273.15Minimum supply temperature
Modelica.SIunits.TemperatureTemSup_max80.0 + 273.15Maximum supply temperature

Connectors

TypeNameDefaultDescription
Modelica.Blocks.Interfaces.RealInputTemOutInput signal connector
Modelica.Blocks.Interfaces.RealOutputyConnector of Real output signal

Revisions

  • Feburary 27, 2019, by Benedikt Leitner:
    Implementation and added User's guide.