blockstorage_control
Information
Control function for storage tank charging de-/activation. Charging starts when the temperature in the top segment T_top falls below the setpoint minus half the bandwith T_top_set - T_top_bandwidth/2. Charging is continued until the temperature at the bottom of the tank reaches its setpoint T_bot_set or until the temperature of the top segement rises above the setpoint plus half the bandwidth T_top_set + T_top_bandwidth/2 (might occur later).
Parameters
| Type | Name | Default | Description |
| Modelica.SIunits.Temperature | T_top_set | 60.0 + 273.15 | Constant temperature setpoint for top layer |
| Modelica.SIunits.Temperature | T_bot_set | 60.0 + 273.15 | Constant temperature setpoint for bottom layer |
| Modelica.SIunits.TemperatureDifference | T_top_bandwidth | 5 | Bandwidth for controller activation |
Revisions
- Feburary 27, 2019, by Benedikt Leitner:
Implementation and added User's guide.