| Types.ApparentPowerModule | SNom | | Nominal converter apparent power in MVA |
| Types.Time | tS | | Integration time step in s |
| QControl |
| Types.PerUnit | IqH1Pu | | Maximum reactive current injection during dip in pu (base UNom, SNom) (generator convention) |
| Types.PerUnit | IqMaxPu | | Maximum reactive current injection in pu (base UNom, SNom) (generator convention) |
| Types.PerUnit | IqMinPu | | Minimum reactive current injection in pu (base UNom, SNom) (generator convention) |
| Types.PerUnit | IqPostPu | | Post-fault reactive current injection in pu (base UNom, SNom) (generator convention) |
| Types.PerUnit | Kiq | | Reactive power PI controller integration gain in pu/s (base UNom, SNom) |
| Types.PerUnit | Kiu | | Voltage PI controller integration gain in pu/s (base UNom, SNom) |
| Types.PerUnit | Kpq | | Reactive power PI controller proportional gain in pu (base UNom, SNom) |
| Types.PerUnit | Kpu | | Voltage PI controller proportional gain in pu (base UNom, SNom) |
| Types.PerUnit | Kqv | | Voltage scaling factor for FRT current in pu (base UNom, SNom) |
| Integer | MqG | | General Q control mode (0-4) : Voltage control (0), Reactive power control (1), Open loop reactive power control (2), Power factor control (3), Open loop power factor control (4) |
| Types.PerUnit | RDropPu | | Resistive component of voltage drop impedance in pu (base UNom, SNom) |
| Types.Time | tPost | | Length of time period where post-fault reactive power is injected, in s |
| Types.Time | tQord | | Reactive power order lag time constant in s |
| Types.VoltageModulePu | UMaxPu | | Maximum voltage in voltage PI controller integral term in pu (base UNom) |
| Types.VoltageModulePu | UMinPu | | Minimum voltage in voltage PI controller integral term in pu (base UNom) |
| Types.VoltageModulePu | UqDipPu | | Voltage threshold for UVRT detection in Q control in pu (base UNom) |
| Types.VoltageModulePu | URef0Pu | | User-defined bias in voltage reference in pu (base UNom) |
| Types.PerUnit | XDropPu | | Inductive component of voltage drop impedance in pu (base UNom, SNom) |
| Operating point |
| Types.ActivePowerPu | P0Pu | | Initial active power at grid terminal in pu (base SnRef) (receptor convention) |
| Types.ReactivePowerPu | Q0Pu | | Initial reactive power at grid terminal in pu (base SnRef) (receptor convention) |
| Types.VoltageModulePu | U0Pu | | Initial voltage amplitude at grid terminal in pu (base UNom) |
| Types.PerUnit | XWT0Pu | | Initial reactive power or voltage reference at grid terminal in pu (base SNom or UNom) (generator convention) |
| Initialization |
| Types.ReactivePowerPu | QMax0Pu | | Initial maximum reactive power at grid terminal in pu (base SNom) (generator convention) |
| Types.ReactivePowerPu | QMin0Pu | | Initial minimum reactive power at grid terminal in pu (base SNom) (generator convention) |