modelBaseWPPPControl
Base active power control module for wind power plants (IEC N°61400-27-1)
Extends from Dynawo.Electrical.Controls.IEC.IEC61400.Parameters.PControlParameters.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Types.ApparentPowerModule | SNom | Nominal converter apparent power in MVA | |
| Types.Time | tS | Integration time step in s | |
| PControlTables | |||
| Real | TablePwpBiasfwpFiltCom11 (from PControlParameters) | 0.95 | |
| Real | TablePwpBiasfwpFiltCom12 (from PControlParameters) | 1 | |
| Real | TablePwpBiasfwpFiltCom21 (from PControlParameters) | 1 | |
| Real | TablePwpBiasfwpFiltCom22 (from PControlParameters) | 0 | |
| Real | TablePwpBiasfwpFiltCom31 (from PControlParameters) | 1.05 | |
| Real | TablePwpBiasfwpFiltCom32 (from PControlParameters) | -1 | |
| Real | TablePwpBiasfwpFiltCom41 (from PControlParameters) | 1.06 | |
| Real | TablePwpBiasfwpFiltCom42 (from PControlParameters) | -1 | |
| Real | TablePwpBiasfwpFiltCom51 (from PControlParameters) | 1.07 | |
| Real | TablePwpBiasfwpFiltCom52 (from PControlParameters) | -1 | |
| Real | TablePwpBiasfwpFiltCom61 (from PControlParameters) | 1.08 | |
| Real | TablePwpBiasfwpFiltCom62 (from PControlParameters) | -1 | |
| Real | TablePwpBiasfwpFiltCom71 (from PControlParameters) | 1.09 | |
| Real | TablePwpBiasfwpFiltCom72 (from PControlParameters) | -1 | |
| Real[:,:] | TablePwpBiasfwpFiltCom (from PControlParameters) | [TablePwpBiasfwpFiltCom11, TablePwpBiasfwpFiltCom12; TablePwpBiasfwpFiltCom21, TablePwpBiasfwpFiltCom22; TablePwpBiasfwpFiltCom31, TablePwpBiasfwpFiltCom32; TablePwpBiasfwpFiltCom41, TablePwpBiasfwpFiltCom42; TablePwpBiasfwpFiltCom51, TablePwpBiasfwpFiltCom52; TablePwpBiasfwpFiltCom61, TablePwpBiasfwpFiltCom62; TablePwpBiasfwpFiltCom71, TablePwpBiasfwpFiltCom72] | Table for defining power variation versus frequency |
| PControlWP | |||
| Types.PerUnit | DPRefMaxPu | Maximum positive ramp rate for PD power reference in pu/s (base SNom) | |
| Types.PerUnit | DPRefMinPu | Minimum negative ramp rate for PD power reference in pu/s (base SNom) | |
| Types.PerUnit | DPwpRefMaxPu | Maximum positive ramp rate for WP power reference in pu/s (base SNom) | |
| Types.PerUnit | DPwpRefMinPu | Minimum negative ramp rate for WP power reference in pu/s (base SNom) | |
| Types.PerUnit | Kiwpp | Power PI controller integration gain in pu/s (base SNom) | |
| Types.PerUnit | Kpwpp | Power PI controller proportional gain in pu (base SNom) | |
| Types.PerUnit | KwppRef | Power reference gain in pu (base SNom) | |
| Types.ActivePowerPu | PKiwppMaxPu | Maximum active power reference from integration in pu (base SNom) | |
| Types.ActivePowerPu | PKiwppMinPu | Minimum active power reference from integration in pu (base SNom) | |
| Types.ActivePowerPu | PRefMaxPu | Maximum PD power reference in pu (base SNom) | |
| Types.ActivePowerPu | PRefMinPu | Minimum PD power reference in pu (base SNom) | |
| Operating point | |||
| Types.ActivePowerPu | P0Pu | Initial active power at grid terminal in pu (base SnRef) (receptor convention) | |
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Blocks.Tables.CombiTable1Ds | combiTable1Ds | ||
| Modelica.Blocks.Math.Feedback | feedback | ||
| Modelica.Blocks.Math.Gain | gain | ||
| Modelica.Blocks.Math.Gain | gain1 | ||
| Modelica.Blocks.Math.Add3 | add31 | ||
| Dynawo.NonElectrical.Blocks.Continuous.AntiWindupIntegrator | antiWindupIntegrator | ||
| Dynawo.NonElectrical.Blocks.Continuous.AbsLimRateLimFeedthroughFreezeLimDetection | absLimRateLimFeedthroughFreezeLimDetection | ||
| Dynawo.NonElectrical.Blocks.NonLinear.RampLimiter | rampLimiter |