modelBaseWPPQControl

Reactive power control base module for wind power plants (IEC N°61400-27-1)

Parameters

TypeNameDefaultDescription
Types.ApparentPowerModuleSNomNominal converter apparent power in MVA
Types.TimetSIntegration time step in s
QControlWP
Types.PerUnitDXRefMaxPuMaximum positive ramp rate for WT reactive power or voltage reference in pu/s (base SNom or UNom) (generator convention)
Types.PerUnitDXRefMinPuMinimum negative ramp rate for WT reactive power or voltage reference in pu/s (base SNom or UNom) (generator convention)
Types.PerUnitKiwpxReactive power or voltage PI controller integral gain in pu/s (base SNom)
Types.PerUnitKpwpxReactive power or voltage PI controller proportional gain in pu (base SNom)
Types.PerUnitKwpqRefReactive power reference gain in pu (base SNom)
Types.PerUnitKwpquVoltage controller cross coupling gain in pu (base SNom)
IntegerMwpqModeControl mode (0 : reactive power reference, 1 : power factor reference, 2 : UQ static, 3 : voltage control)
Types.TimetUqFiltTime constant for the UQ static mode in s
Types.VoltageModulePuUwpqDipPuVoltage threshold for UVRT detection in pu (base UNom)
Types.PerUnitXKiwpxMaxPuMaximum WT reactive power or voltage reference from integration in pu (base SNom or UNom) (generator convention)
Types.PerUnitXKiwpxMinPuMinimum WT reactive power or voltage reference from integration in pu (base SNom or UNom) (generator convention)
Types.PerUnitXRefMaxPuMaximum WT reactive power or voltage reference in pu (base SNom or UNom) (generator convention)
Types.PerUnitXRefMinPuMinimum WT reactive power or voltage reference in pu (base SNom or UNom) (generator convention)
Operating point
Types.ActivePowerPuP0PuInitial active power at grid terminal in pu (base SnRef) (receptor convention)
Types.ReactivePowerPuQ0PuInitial reactive power at grid terminal in pu (base SnRef) (receptor convention)
Types.VoltageModulePuU0PuInitial voltage amplitude at grid terminal in pu (base UNom)
Types.PerUnitX0PuInitial reactive power or voltage reference at grid terminal in pu (base SNom or UNom) (generator convention)
Types.PerUnitXWT0PuInitial reactive power or voltage reference at grid terminal in pu (base SNom or UNom) (generator convention)

Components

TypeNameDefaultDescription
Modelica.Blocks.Math.Feedbackfeedback
Modelica.Blocks.Tables.CombiTable1DscombiTable1Ds2
Modelica.Blocks.Math.Feedbackfeedback1
Modelica.Blocks.Logical.LessThresholdlessThreshold
Dynawo.NonElectrical.Blocks.NonLinear.MultiSwitchmultiSwitch
Modelica.Blocks.Sources.IntegerConstantintegerConstant
Modelica.Blocks.Math.Productproduct
Modelica.Blocks.Math.Gaingain
Modelica.Blocks.Math.Gaingain1
Modelica.Blocks.Math.Gaingain2
Dynawo.NonElectrical.Blocks.NonLinear.MultiSwitchmultiSwitch1
Modelica.Blocks.Math.Feedbackfeedback2
Modelica.Blocks.Sources.Constantconst
Modelica.Blocks.Math.Add3add3
Dynawo.NonElectrical.Blocks.Continuous.AbsLimRateLimFeedthroughFreezeLimDetectionabsLimRateLimFeedthroughFreezeLimDetection
Dynawo.NonElectrical.Blocks.Continuous.AbsLimRateLimFirstOrderFreezeabsLimRateLimFirstOrderFreeze
Modelica.Blocks.MathBoolean.Oror2
Dynawo.NonElectrical.Blocks.Continuous.AntiWindupIntegratorantiWindupIntegrator