| Types.ApparentPowerModule | SNom | | Nominal converter apparent power in MVA |
| Types.Time | tS | | Integration time step in s |
| QControlWP |
| Types.PerUnit | DXRefMaxPu | | Maximum positive ramp rate for WT reactive power or voltage reference in pu/s (base SNom or UNom) (generator convention) |
| Types.PerUnit | DXRefMinPu | | Minimum negative ramp rate for WT reactive power or voltage reference in pu/s (base SNom or UNom) (generator convention) |
| Types.PerUnit | Kiwpx | | Reactive power or voltage PI controller integral gain in pu/s (base SNom) |
| Types.PerUnit | Kpwpx | | Reactive power or voltage PI controller proportional gain in pu (base SNom) |
| Types.PerUnit | KwpqRef | | Reactive power reference gain in pu (base SNom) |
| Types.PerUnit | Kwpqu | | Voltage controller cross coupling gain in pu (base SNom) |
| Integer | MwpqMode | | Control mode (0 : reactive power reference, 1 : power factor reference, 2 : UQ static, 3 : voltage control) |
| Types.Time | tUqFilt | | Time constant for the UQ static mode in s |
| Types.VoltageModulePu | UwpqDipPu | | Voltage threshold for UVRT detection in pu (base UNom) |
| Types.PerUnit | XKiwpxMaxPu | | Maximum WT reactive power or voltage reference from integration in pu (base SNom or UNom) (generator convention) |
| Types.PerUnit | XKiwpxMinPu | | Minimum WT reactive power or voltage reference from integration in pu (base SNom or UNom) (generator convention) |
| Types.PerUnit | XRefMaxPu | | Maximum WT reactive power or voltage reference in pu (base SNom or UNom) (generator convention) |
| Types.PerUnit | XRefMinPu | | Minimum WT reactive power or voltage reference in pu (base SNom or UNom) (generator convention) |
| Operating point |
| Types.ActivePowerPu | P0Pu | | Initial active power at grid terminal in pu (base SnRef) (receptor convention) |
| Types.ReactivePowerPu | Q0Pu | | Initial reactive power at grid terminal in pu (base SnRef) (receptor convention) |
| Types.VoltageModulePu | U0Pu | | Initial voltage amplitude at grid terminal in pu (base UNom) |
| Types.PerUnit | X0Pu | | Initial reactive power or voltage reference at grid terminal in pu (base SNom or UNom) (generator convention) |
| Types.PerUnit | XWT0Pu | | Initial reactive power or voltage reference at grid terminal in pu (base SNom or UNom) (generator convention) |