modelPControl4B2020

Active power control module for type 4B wind turbines (IEC N°61400-27-1:2020)

Extends from Dynawo.Electrical.Controls.IEC.IEC61400.BaseClasses.BasePControl4 (Base active power control module for type 4 wind turbines (IEC N°61400-27-1)).

Parameters

TypeNameDefaultDescription
Types.ApparentPowerModuleSNom (from BasePControl4)Nominal converter apparent power in MVA
Types.TimetSIntegration time step in s
PControl
Types.PerUnitKpaw (from BasePControl4)Anti-windup gain for the integrator of the ramp-limited first order in pu/s (base SNom)
Types.PerUnitDPMaxP4BPuMaximum WT power ramp rate in pu/s (base SNom) (generator convention)
Types.PerUnitDPRefMax4BPuMaximum WT reference power ramp rate in pu/s (base SNom) (generator convention)
Types.PerUnitDPRefMin4BPuMinimum WT reference power ramp rate in pu/s (base SNom) (generator convention)
BooleanMpUScaleVoltage scaling for power reference during voltage dip (true: u scaling, false: no scaling)
Types.TimetPAeroAerodynamic power response time constant in s
Types.TimetPOrdP4BPower order lag time constant in s
Types.VoltageModulePuUpDipPuVoltage threshold to activate voltage scaling for power reference during voltage dip in pu (base UNom)
Initialization
Types.PerUnitIpMax0Pu (from BasePControl4)Initial maximum active current at converter terminal in pu (base UNom, SNom) (generator convention)
Operating point
Types.ActivePowerPuP0Pu (from BasePControl4)Initial active power at grid terminal in pu (base SnRef) (receptor convention)
Types.VoltageModulePuU0Pu (from BasePControl4)Initial voltage amplitude at grid terminal in pu (base UNom)

Connectors

TypeNameDefaultDescription
Modelica.Blocks.Interfaces.RealInputipMaxPu (from BasePControl4)Maximum active current at converter terminal in pu (base UNom, SNom) (generator convention)
Modelica.Blocks.Interfaces.RealInputPWTRefPu (from BasePControl4)Active power reference at grid terminal in pu (base SNom) (generator convention)
Modelica.Blocks.Interfaces.RealOutputipCmdPu (from BasePControl4)Active current command at converter terminal in pu (base UNom, SNom) (generator convention)
Modelica.Blocks.Interfaces.RealInputUWTCFiltPuFiltered voltage amplitude at grid terminal in pu (base UNom)
Modelica.Blocks.Interfaces.RealInputUWTCPuVoltage amplitude at grid terminal in pu (base UNom)
Modelica.Blocks.Interfaces.RealOutputPAeroPuAerodynamic power in pu (base SNom) (generator convention)
Modelica.Blocks.Interfaces.RealInputomegaGenPuGenerator angular frequency in pu (base omegaNom)

Components

TypeNameDefaultDescription
Modelica.Blocks.Math.Productproduct1 (from BasePControl4)
Modelica.Blocks.Math.Divisiondivision (from BasePControl4)
Modelica.Blocks.Math.Maxmax (from BasePControl4)
Modelica.Blocks.Sources.Constantconst (from BasePControl4)
Dynawo.NonElectrical.Blocks.Continuous.AbsLimRateLimFirstOrderAntiWindupabsLimRateLimFirstOrderAntiWindup (from BasePControl4)
Modelica.Blocks.Sources.Constantconst2 (from BasePControl4)
Modelica.Blocks.Logical.Andand1
Modelica.Blocks.Sources.BooleanConstantbooleanConstant
Modelica.Blocks.Sources.Constantconst1
Modelica.Blocks.Continuous.FirstOrderfirstOrder
Modelica.Blocks.Logical.Lessless
Modelica.Blocks.Math.Productproduct
Modelica.Blocks.Math.Productproduct2
Dynawo.NonElectrical.Blocks.NonLinear.RampLimiterrampLimiter
Modelica.Blocks.Logical.Switchswitch1