modelReactivePowerControlLoop2
Simplified Reactive Power Control Loop model for renewable energy sources
Information
The reactive control loop gets a level K from the secondary voltage control and transforms it into a voltage reference for the generator voltage regulator
Parameters
| Type | Name | Default | Description |
| Types.PerUnit | CqMaxPu | | Max of Cq in the different exploitation schemes in pu (base UNom, QNom) |
| Types.VoltageModulePu | DeltaURefMaxPu | | Maximum of deltaURef on one activation period (URef(t+1) - URef(t)) in pu (base UNom) |
| Types.ReactivePowerPu | QrPu | | Participation factor of the generator to the secondary voltage control in pu (base QNom) |
| Types.Time | Tech | | Sampling time in s |
| Types.Time | Tech2 | Tech | Integrator's time constant equal to sampling time in s |
| Types.Time | Ti | | Filters' time constant in s |
| Types.VoltageModulePu | UStatorRefMinPu | 0.85 | Minimum reference voltage for the generator voltage regulator in pu (base UNom) |
| Types.VoltageModulePu | UStatorRefMaxPu | 1.15 | Maximum reference voltage for the generator voltage regulator in pu (base UNom) |
| Boolean | limUQDown0 | | Whether the minimum reactive power limits are reached or not (from generator voltage regulator), start value |
| Boolean | limUQUp0 | | Whether the maximum reactive power limits are reached or not (from generator voltage regulator), start value |
| Types.ReactivePowerPu | QStator0Pu | | Start value of the generator stator reactive power in pu (base QNomAlt) (generator convention) |
| Types.VoltageModulePu | UStatorRef0Pu | | Start value of the generator stator voltage reference in pu (base UNom) |