modelMAXEX2
Overexcitation limitation for standard voltage regulator
Parameters
| Type | Name | Default | Description |
| Types.CurrentModulePu | Ifd1Pu | 1.1 | Field current of first characteristic point in pu (base SNom, user-selected base voltage) |
| Types.CurrentModulePu | Ifd2Pu | 1.2 | Field current of second characteristic point in pu (base SNom, user-selected base voltage) |
| Types.CurrentModulePu | Ifd3Pu | 1.5 | Field current of third characteristic point in pu (base SNom, user-selected base voltage) |
| Types.CurrentModule | IfdRated | 2.6355 | Synchronous generator rated field current in kA |
| Types.PerUnit | Kmx | 0.2 | Integrator gain of overexcitation limitation |
| Types.Time | t1 | 60 | Time of first characteristic point in s |
| Types.Time | t2 | 30 | Time of second characteristic point in s |
| Types.Time | t3 | 15 | Time of third characteristic point in s |
| Types.PerUnit | ULowPu | -0.05 | Lower limit of overexcitation limitation output voltage in pu (base UNom) |
| Types.PerUnit[:,:] | FOel | [t3 - 1, Ifd3Pu; t3, Ifd3Pu; t2, Ifd2Pu; t1, Ifd1Pu; t1 + 1, Ifd1Pu] | Time characteristic of the overexcitation limitation |
| Types.CurrentModulePu | Ifd0Pu | | Initial generator field current in pu (base SNom, user-selected base voltage) |