modelBaseTapChangerPhaseShifterTarget

Base model for tap-changers and phase-shifters ensuring that the monitored value remains close to a target value

Extends from BaseTapChangerPhaseShifterInterval (Base model for tap-changers and phase-shifters which tries to keep a value within a given interval).

Parameters

TypeNameDefaultDescription
IntegerNbSwitchOffSignals (from SwitchOffLogic)Number of switch-off signals to take into account in inputs
BooleanSwitchOffSignal10 (from SwitchOffLogic)falseInitial switch-off signal 1
BooleanSwitchOffSignal20 (from SwitchOffLogic)falseInitial switch-off signal 2
BooleanSwitchOffSignal30 (from SwitchOffLogic)falseInitial switch-off signal 3
BooleanRunning0 (from SwitchOffLogic)if NbSwitchOffSignals >= 3 then not (SwitchOffSignal10 or SwitchOffSignal20 or SwitchOffSignal30) elseif NbSwitchOffSignals >= 2 then not (SwitchOffSignal10 or SwitchOffSignal20) else not SwitchOffSignal10Indicates if the component is initially running or not
AutomatonType (from SwitchOffTapChangerPhaseShifter)
Types.Timet1st (from TapChangerPhaseShifterParams)Time lag before changing the first tap in s
Types.TimetNext (from TapChangerPhaseShifterParams)Time lag before changing subsequent taps in s
IntegertapMin (from TapChangerPhaseShifterParams)Minimum tap
IntegertapMax (from TapChangerPhaseShifterParams)Maximum tap
Booleanregulating0 (from TapChangerPhaseShifterParams)Whether the tap-changer/phase-shifter is initially regulating
Booleanlocked0 (from TapChangerPhaseShifterParams)not regulating0Whether the tap-changer/phase-shifter is initially locked
Booleanrunning0 (from TapChangerPhaseShifterParams)trueWhether the tap-changer/phase-shifter is initially running
RealvalueToMonitor0 (from TapChangerPhaseShifterParams)Initial monitored value (unit depending on the monitored variable unit)
Integertap0 (from TapChangerPhaseShifterParams)Initial tap
Statestate0 (from TapChangerPhaseShifterParams)Initial state
RealvalueMax (from BaseTapChangerPhaseShifter)Threshold above which the tap-changer/phase-shifter will take action (unit depending on the monitored variable unit)
RealvalueMin (from BaseTapChangerPhaseShifterInterval)Minimum allowed value (unit depending on the monitored variable unit)
BooleanincreaseTapToIncreaseValue (from BaseTapChangerPhaseShifterInterval)Whether increasing the tap will increase the monitored value
BooleanincreaseTapToDecreaseValue (from BaseTapChangerPhaseShifterInterval)not decreaseTapToDecreaseValueWhether increasing the tap will decrease the monitored value
BooleandecreaseTapToIncreaseValue (from BaseTapChangerPhaseShifterInterval)not increaseTapToIncreaseValueWhether decreasing the tap will increase the monitored value
BooleandecreaseTapToDecreaseValue (from BaseTapChangerPhaseShifterInterval)increaseTapToIncreaseValueWhether decreasing the tap will decrease the monitored value
RealtargetValueTarget value (unit depending on the monitored variable unit)
RealdeadBandAcceptable dead-band next to the target value (unit depending on the monitored variable unit)

Connectors

TypeNameDefaultDescription
Dynawo.Connectors.BPinswitchOffSignal1 (from SwitchOffLogic)Switch-off signal 1
Dynawo.Connectors.BPinswitchOffSignal2 (from SwitchOffLogic)Switch-off signal 2
Dynawo.Connectors.BPinswitchOffSignal3 (from SwitchOffLogic)Switch-off signal 3
Dynawo.Connectors.BPinrunning (from SwitchOffLogic)Indicates if the component is running or not
Dynawo.Connectors.ImPinvalueToMonitor (from BaseTapChangerPhaseShifter)Monitored value (unit depending on the monitored variable unit)
Dynawo.Connectors.ZPintap (from BaseTapChangerPhaseShifter)Current tap
Dynawo.Connectors.BPinAutomatonExists (from BaseTapChangerPhaseShifter)Pin to indicate to deactivate internal automaton

Components

TypeNameDefaultDescription
Booleanlocked (from BaseTapChangerPhaseShifter)Whether the tap-changer/phase-shifter is locked
Statestate (from BaseTapChangerPhaseShifter)State of the tap-changer/phase-shifter