modelGeneratorPVQNomAltPar_INIT

Initialisation model for generator PV based on SignalN for the frequency handling. In this model, QNomAlt is a parameter.

Extends from BaseClasses_INIT.BaseGeneratorSignalN_INIT (Base initialization model for SignalN generator models), AdditionalIcons.Init.

Parameters

TypeNameDefaultDescription
Types.ComplexCurrentPuiStart0Pu (from BaseGeneratorParameters_INIT)Complex(0, 0)Start value of complex current at terminal in pu (base UNom, SnRef) (receptor convention)
Types.ActivePowerPuP0Pu (from BaseGeneratorParameters_INIT)Start value of active power at terminal in pu (base SnRef) (receptor convention)
Types.ReactivePowerPuQ0Pu (from BaseGeneratorParameters_INIT)Start value of reactive power at terminal in pu (base SnRef) (receptor convention)
Types.VoltageModulePuU0Pu (from BaseGeneratorParameters_INIT)Start value of voltage amplitude at terminal in pu (base UNom)
Types.AngleUPhase0 (from BaseGeneratorParameters_INIT)Start value of voltage angle at terminal in rad
Types.ActivePowerPuPMax (from BaseGeneratorSignalN_INIT)Maximum active power in MW
Types.ActivePowerPuPMin (from BaseGeneratorSignalN_INIT)Minimum active power in MW
Types.ReactivePowerPuQMax (from BaseGeneratorSignalN_INIT)Maximum reactive power in Mvar
Types.ReactivePowerPuQMin (from BaseGeneratorSignalN_INIT)Minimum reactive power in Mvar
Types.ReactivePowerQNomAltNominal reactive power of the generator on alternator side in Mvar
Types.VoltageModulePuURef0PuStart value of the voltage regulation set point in pu (base UNom)

Components

TypeNameDefaultDescription
Types.ActivePowerPuPGen0Pu (from BaseGeneratorParameters_INIT)Start value of active power at terminal in pu (base SnRef) (generator convention)
Types.ReactivePowerPuQGen0Pu (from BaseGeneratorParameters_INIT)Start value of reactive power at terminal in pu (base SnRef) (generator convention)
Types.ComplexVoltagePuu0Pu (from BaseGeneratorParameters_INIT)Start value of complex voltage at terminal in pu (base UNom)
Types.ComplexApparentPowerPus0Pu (from BaseGeneratorParameters_INIT)Start value of complex apparent power at terminal in pu (base SnRef) (receptor convention)
Types.ComplexCurrentPui0Pu (from BaseGeneratorParameters_INIT)Start value of complex current at terminal in pu (base UNom, SnRef) (receptor convention)
BooleanlimUQDown0 (from BaseGeneratorSignalN_INIT)Whether the minimum reactive power limits are reached or not (from generator voltage regulator), start value
BooleanlimUQUp0 (from BaseGeneratorSignalN_INIT)Whether the maximum reactive power limits are reached or not (from generator voltage regulator), start value
Types.ActivePowerPuPMaxPu (from BaseGeneratorSignalN_INIT)Maximum active power in pu (base SnRef)
Types.ReactivePowerPuQMaxPu (from BaseGeneratorSignalN_INIT)Maximum reactive power in pu (base SnRef)
Types.ActivePowerPuPMinPu (from BaseGeneratorSignalN_INIT)Minimum active power in pu (base SnRef)
Types.ReactivePowerPuQMinPu (from BaseGeneratorSignalN_INIT)Minimum reactive power in pu (base SnRef)
QStatusqStatus0 (from BaseGeneratorSignalN_INIT)Start voltage regulation status: Standard, AbsorptionMax, GenerationMax
Types.ReactivePowerPuQStator0PuStart value of stator reactive power in pu (base QNomAlt) (generator convention)
Types.VoltageModulePuURef0PuVarStart value of the voltage regulation set point in pu (base UNom)