| Types.ApparentPowerModule | SNom | | Nominal apparent power of the injector (in MVA) |
| Types.CurrentModulePu | IMaxPu | | Maximum current of the injector in pu (base UNom, SNom) |
| Boolean | PPriority | | If true, prioritise active power over reactive power |
| Real | KpPll | 3 | PLL proportional coefficient |
| Real | KiPll | 10 | PLL integral coefficient |
| Types.Time | tFilterU | | Voltage measurement first order time constant in s |
| Types.Time | tFilterOmega | | First order time constant for the frequency estimation in s |
| Types.Time | tRateLim | 1e-3 | Current slew limiter delay in s |
| Types.Time | tP | | P measurement first order time constant in s |
| Types.Time | tG | | Output current time constant in s |
| Types.Time | tPord | | Active power time constant in s |
| Types.Time | tIq | | Reactive current time constant in s |
| Types.AngularVelocityPu | FDbd1Pu | | Lower value of frequency dead zone in pu (base omegaNom) |
| Types.AngularVelocityPu | FDbd2Pu | | Upper value of frequency dead zone in pu (base omegaNom) |
| Real | DdnPu | | Power reduction factor for over-frequency in pu (base SNom) |
| Real | DupPu | | Power increase factor for under-frequency in pu (base SNom) |
| Types.AngularVelocityPu | FEMaxPu | | Maximum frequency error correction in pu (base omegaNom) |
| Types.AngularVelocityPu | FEMinPu | | Minimum frequency error correction in pu (base omegaNom) |
| Real | Kpg | | PI proportional coefficient of frequency support in pu (base SNom, omegaNom) |
| Real | Kig | | PI integral coefficient of frequency support in pu (base SNom, omegaNom) |
| Types.ActivePowerPu | PMaxPu | | Maximum active power in pu (base SNom) |
| Types.ActivePowerPu | PMinPu | | Minimum active power in pu (base SNom) |
| Types.PerUnit | DPMaxPu | | Maximum active power rise rate in pu (base SNom) |
| Types.PerUnit | DPMinPu | | Minimum active power drop rate in pu (base SNom) |
| Boolean | FreqFlag | | True if inverters support frequency |
| Types.AngularVelocityPu | OmegaMaxPu | | Maximum frequency before disconnection in pu (base omegaNom) |
| Types.AngularVelocityPu | OmegaMinPu | | Minimum frequency before start of disconnections in pu (base omegaNom) |
| Types.Time | tOmegaMaxPu | | Time-lag for over-frequency trips in s |
| Types.Time | tOmegaMinPu | | Time-lag for under-frequency trips in s |
| Types.CurrentModulePu | IpRateLimMax | | Maximum rise rate of the active current in pu (base SNom) |
| Types.CurrentModulePu | IpRateLimMin | | Minimum drop rate of the active current in pu (base SNom) |
| Boolean | PfFlag | | True for constant power factor, false for constant reactive power |
| Types.VoltageModulePu | VRefPu | 1 | Voltage reference in pu (base UNom) |
| Types.VoltageModulePu | Dbd1Pu | | Lower value of voltage dead zone in pu (base UNom) |
| Types.VoltageModulePu | Dbd2Pu | | Upper value of voltage dead zone in pu (base UNom) |
| Real | Kqv | | Proportional coefficient of reactive support in pu (base SNom, UNom) |
| Types.CurrentModulePu | Iqh1 | | Maximum reactive support current command (base SNom, UNom) |
| Types.CurrentModulePu | Iql1 | | Maximum reactive support current command (base SNom, UNom) |
| Types.ComplexCurrentPu | i0Pu | | Start value of complex current at terminal in pu (base UNom, SnRef) (receptor convention) |
| Types.PerUnit | Id0Pu | | Start value of d-axs current at injector in pu (base UNom, SNom) (generator convention) |
| Types.PerUnit | Iq0Pu | | Start value of q-axis current at injector in pu (base UNom, SNom) (generator convention) |
| Types.ActivePowerPu | P0Pu | | Start value of active power at terminal in pu (base SnRef) (receptor convention) |
| Types.PerUnit | PF0 | | Start value of power factor |
| Types.ReactivePowerPu | Q0Pu | | Start value of reactive power at terminal in pu (base SnRef) (receptor convention) |
| Types.ComplexApparentPowerPu | s0Pu | | Start value of complex apparent power at terminal in pu (base SnRef) (receptor convention) |
| Types.VoltageModulePu | U0Pu | | Start value of voltage magnitude at terminal in pu (base UNom) |
| Types.ComplexVoltagePu | u0Pu | | Start value of complex voltage at terminal in pu (base UNom) |
| Types.Angle | UPhase0 | | Start value of voltage phase angle at terminal in rad |