modelWT4BCurrentSource2015
Wind Turbine Type 4B model from IEC 61400-27-1:2015 standard : measurement, PLL, protection, PControl, QControl, limiters, electrical and generator modules
Extends from Dynawo.Electrical.Wind.IEC.BaseClasses.BaseWT4 (Base model for Wind Turbine Type 4 from IEC 61400-27-1 standard).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Types.ApparentPowerModule | SNom (from BaseWT4) | Nominal converter apparent power in MVA | |
| Types.Time | tS (from BaseWT4) | Integration time step in s | |
| CurrentLimitTables | |||
| Real | TableIpMaxUwt11 (from CurrentLimitParameters) | 0 | |
| Real | TableIpMaxUwt12 (from CurrentLimitParameters) | 0 | |
| Real | TableIpMaxUwt21 (from CurrentLimitParameters) | 0.1 | |
| Real | TableIpMaxUwt22 (from CurrentLimitParameters) | 0 | |
| Real | TableIpMaxUwt31 (from CurrentLimitParameters) | 0.15 | |
| Real | TableIpMaxUwt32 (from CurrentLimitParameters) | 1 | |
| Real | TableIpMaxUwt41 (from CurrentLimitParameters) | 0.9 | |
| Real | TableIpMaxUwt42 (from CurrentLimitParameters) | 1 | |
| Real | TableIpMaxUwt51 (from CurrentLimitParameters) | 0.925 | |
| Real | TableIpMaxUwt52 (from CurrentLimitParameters) | 1 | |
| Real | TableIpMaxUwt61 (from CurrentLimitParameters) | 1.075 | |
| Real | TableIpMaxUwt62 (from CurrentLimitParameters) | 1.0001 | |
| Real | TableIpMaxUwt71 (from CurrentLimitParameters) | 1.1 | |
| Real | TableIpMaxUwt72 (from CurrentLimitParameters) | 1.0001 | |
| Real[:,:] | TableIpMaxUwt (from CurrentLimitParameters) | [TableIpMaxUwt11, TableIpMaxUwt12; TableIpMaxUwt21, TableIpMaxUwt22; TableIpMaxUwt31, TableIpMaxUwt32; TableIpMaxUwt41, TableIpMaxUwt42; TableIpMaxUwt51, TableIpMaxUwt52; TableIpMaxUwt61, TableIpMaxUwt62; TableIpMaxUwt71, TableIpMaxUwt72] | Voltage dependency of active current limits |
| Real | TableIqMaxUwt11 (from CurrentLimitParameters) | 0 | |
| Real | TableIqMaxUwt12 (from CurrentLimitParameters) | 0 | |
| Real | TableIqMaxUwt21 (from CurrentLimitParameters) | 0.1 | |
| Real | TableIqMaxUwt22 (from CurrentLimitParameters) | 0 | |
| Real | TableIqMaxUwt31 (from CurrentLimitParameters) | 0.15 | |
| Real | TableIqMaxUwt32 (from CurrentLimitParameters) | 1 | |
| Real | TableIqMaxUwt41 (from CurrentLimitParameters) | 0.9 | |
| Real | TableIqMaxUwt42 (from CurrentLimitParameters) | 1 | |
| Real | TableIqMaxUwt51 (from CurrentLimitParameters) | 0.925 | |
| Real | TableIqMaxUwt52 (from CurrentLimitParameters) | 0.33 | |
| Real | TableIqMaxUwt61 (from CurrentLimitParameters) | 1.075 | |
| Real | TableIqMaxUwt62 (from CurrentLimitParameters) | 0.33 | |
| Real | TableIqMaxUwt71 (from CurrentLimitParameters) | 1.1 | |
| Real | TableIqMaxUwt72 (from CurrentLimitParameters) | 1 | |
| Real | TableIqMaxUwt81 (from CurrentLimitParameters) | 1.1001 | |
| Real | TableIqMaxUwt82 (from CurrentLimitParameters) | 1 | |
| Real[:,:] | TableIqMaxUwt (from CurrentLimitParameters) | [TableIqMaxUwt11, TableIqMaxUwt12; TableIqMaxUwt21, TableIqMaxUwt22; TableIqMaxUwt31, TableIqMaxUwt32; TableIqMaxUwt41, TableIqMaxUwt42; TableIqMaxUwt51, TableIqMaxUwt52; TableIqMaxUwt61, TableIqMaxUwt62; TableIqMaxUwt71, TableIqMaxUwt72; TableIqMaxUwt81, TableIqMaxUwt82] | Voltage dependency of reactive current limits |
| GridProtectionTables | |||
| Real | TabletUoverUwtfilt11 (from GridProtectionParameters) | 1 | |
| Real | TabletUoverUwtfilt12 (from GridProtectionParameters) | 0.33 | |
| Real | TabletUoverUwtfilt21 (from GridProtectionParameters) | 1.5 | |
| Real | TabletUoverUwtfilt22 (from GridProtectionParameters) | 0.33 | |
| Real | TabletUoverUwtfilt31 (from GridProtectionParameters) | 2 | |
| Real | TabletUoverUwtfilt32 (from GridProtectionParameters) | 0.33 | |
| Real | TabletUoverUwtfilt41 (from GridProtectionParameters) | 2.01 | |
| Real | TabletUoverUwtfilt42 (from GridProtectionParameters) | 0.33 | |
| Real | TabletUoverUwtfilt51 (from GridProtectionParameters) | 2.02 | |
| Real | TabletUoverUwtfilt52 (from GridProtectionParameters) | 0.33 | |
| Real | TabletUoverUwtfilt61 (from GridProtectionParameters) | 2.03 | |
| Real | TabletUoverUwtfilt62 (from GridProtectionParameters) | 0.33 | |
| Real | TabletUoverUwtfilt71 (from GridProtectionParameters) | 2.04 | |
| Real | TabletUoverUwtfilt72 (from GridProtectionParameters) | 0.33 | |
| Real | TabletUoverUwtfilt81 (from GridProtectionParameters) | 2.05 | |
| Real | TabletUoverUwtfilt82 (from GridProtectionParameters) | 0.33 | |
| Real[:,:] | TabletUoverUwtfilt (from GridProtectionParameters) | [TabletUoverUwtfilt11, TabletUoverUwtfilt12; TabletUoverUwtfilt21, TabletUoverUwtfilt22; TabletUoverUwtfilt31, TabletUoverUwtfilt32; TabletUoverUwtfilt41, TabletUoverUwtfilt42; TabletUoverUwtfilt51, TabletUoverUwtfilt52; TabletUoverUwtfilt61, TabletUoverUwtfilt62; TabletUoverUwtfilt71, TabletUoverUwtfilt72; TabletUoverUwtfilt81, TabletUoverUwtfilt82] | Disconnection time versus over voltage lookup table |
| Real | TabletUunderUwtfilt11 (from GridProtectionParameters) | 0 | |
| Real | TabletUunderUwtfilt12 (from GridProtectionParameters) | 0.33 | |
| Real | TabletUunderUwtfilt21 (from GridProtectionParameters) | 0.5 | |
| Real | TabletUunderUwtfilt22 (from GridProtectionParameters) | 0.33 | |
| Real | TabletUunderUwtfilt31 (from GridProtectionParameters) | 1 | |
| Real | TabletUunderUwtfilt32 (from GridProtectionParameters) | 0.33 | |
| Real | TabletUunderUwtfilt41 (from GridProtectionParameters) | 1.01 | |
| Real | TabletUunderUwtfilt42 (from GridProtectionParameters) | 0.33 | |
| Real | TabletUunderUwtfilt51 (from GridProtectionParameters) | 1.02 | |
| Real | TabletUunderUwtfilt52 (from GridProtectionParameters) | 0.33 | |
| Real | TabletUunderUwtfilt61 (from GridProtectionParameters) | 1.03 | |
| Real | TabletUunderUwtfilt62 (from GridProtectionParameters) | 0.33 | |
| Real | TabletUunderUwtfilt71 (from GridProtectionParameters) | 1.04 | |
| Real | TabletUunderUwtfilt72 (from GridProtectionParameters) | 0.33 | |
| Real[:,:] | TabletUunderUwtfilt (from GridProtectionParameters) | [TabletUunderUwtfilt11, TabletUunderUwtfilt12; TabletUunderUwtfilt21, TabletUunderUwtfilt22; TabletUunderUwtfilt31, TabletUunderUwtfilt32; TabletUunderUwtfilt41, TabletUunderUwtfilt42; TabletUunderUwtfilt51, TabletUunderUwtfilt52; TabletUunderUwtfilt61, TabletUunderUwtfilt62; TabletUunderUwtfilt71, TabletUunderUwtfilt72] | Disconnection time versus under voltage lookup table |
| Real | Tabletfoverfwtfilt11 (from GridProtectionParameters) | 1 | |
| Real | Tabletfoverfwtfilt12 (from GridProtectionParameters) | 0.33 | |
| Real | Tabletfoverfwtfilt21 (from GridProtectionParameters) | 1.5 | |
| Real | Tabletfoverfwtfilt22 (from GridProtectionParameters) | 0.33 | |
| Real | Tabletfoverfwtfilt31 (from GridProtectionParameters) | 2 | |
| Real | Tabletfoverfwtfilt32 (from GridProtectionParameters) | 0.33 | |
| Real | Tabletfoverfwtfilt41 (from GridProtectionParameters) | 2.01 | |
| Real | Tabletfoverfwtfilt42 (from GridProtectionParameters) | 0.33 | |
| Real[:,:] | Tabletfoverfwtfilt (from GridProtectionParameters) | [Tabletfoverfwtfilt11, Tabletfoverfwtfilt12; Tabletfoverfwtfilt21, Tabletfoverfwtfilt22; Tabletfoverfwtfilt31, Tabletfoverfwtfilt32; Tabletfoverfwtfilt41, Tabletfoverfwtfilt42] | Disconnection time versus over frequency lookup table |
| Real | Tabletfunderfwtfilt11 (from GridProtectionParameters) | 0 | |
| Real | Tabletfunderfwtfilt12 (from GridProtectionParameters) | 0.33 | |
| Real | Tabletfunderfwtfilt21 (from GridProtectionParameters) | 0.5 | |
| Real | Tabletfunderfwtfilt22 (from GridProtectionParameters) | 0.33 | |
| Real | Tabletfunderfwtfilt31 (from GridProtectionParameters) | 1 | |
| Real | Tabletfunderfwtfilt32 (from GridProtectionParameters) | 0.33 | |
| Real | Tabletfunderfwtfilt41 (from GridProtectionParameters) | 1.01 | |
| Real | Tabletfunderfwtfilt42 (from GridProtectionParameters) | 0.33 | |
| Real | Tabletfunderfwtfilt51 (from GridProtectionParameters) | 1.02 | |
| Real | Tabletfunderfwtfilt52 (from GridProtectionParameters) | 0.33 | |
| Real | Tabletfunderfwtfilt61 (from GridProtectionParameters) | 1.03 | |
| Real | Tabletfunderfwtfilt62 (from GridProtectionParameters) | 0.33 | |
| Real[:,:] | Tabletfunderfwtfilt (from GridProtectionParameters) | [Tabletfunderfwtfilt11, Tabletfunderfwtfilt12; Tabletfunderfwtfilt21, Tabletfunderfwtfilt22; Tabletfunderfwtfilt31, Tabletfunderfwtfilt32; Tabletfunderfwtfilt41, Tabletfunderfwtfilt42; Tabletfunderfwtfilt51, Tabletfunderfwtfilt52; Tabletfunderfwtfilt61, Tabletfunderfwtfilt62] | Disconnection time versus under frequency lookup table |
| QLimitTables | |||
| Real | TableQMaxUwtcFilt11 (from QLimitParameters) | 0 | |
| Real | TableQMaxUwtcFilt12 (from QLimitParameters) | 0 | |
| Real | TableQMaxUwtcFilt21 (from QLimitParameters) | 0.001 | |
| Real | TableQMaxUwtcFilt22 (from QLimitParameters) | 0 | |
| Real | TableQMaxUwtcFilt31 (from QLimitParameters) | 0.8 | |
| Real | TableQMaxUwtcFilt32 (from QLimitParameters) | 0.33 | |
| Real | TableQMaxUwtcFilt41 (from QLimitParameters) | 1.2 | |
| Real | TableQMaxUwtcFilt42 (from QLimitParameters) | 0.33 | |
| Real | TableQMaxUwtcFilt51 (from QLimitParameters) | 1.21 | |
| Real | TableQMaxUwtcFilt52 (from QLimitParameters) | 0.33 | |
| Real | TableQMaxUwtcFilt61 (from QLimitParameters) | 1.22 | |
| Real | TableQMaxUwtcFilt62 (from QLimitParameters) | 0.33 | |
| Real[:,:] | TableQMaxUwtcFilt (from QLimitParameters) | [TableQMaxUwtcFilt11, TableQMaxUwtcFilt12; TableQMaxUwtcFilt21, TableQMaxUwtcFilt22; TableQMaxUwtcFilt31, TableQMaxUwtcFilt32; TableQMaxUwtcFilt41, TableQMaxUwtcFilt42; TableQMaxUwtcFilt51, TableQMaxUwtcFilt52; TableQMaxUwtcFilt61, TableQMaxUwtcFilt62] | Voltage dependency of reactive power maximum limit |
| Real | TableQMinUwtcFilt11 (from QLimitParameters) | 0 | |
| Real | TableQMinUwtcFilt12 (from QLimitParameters) | 0 | |
| Real | TableQMinUwtcFilt21 (from QLimitParameters) | 0.001 | |
| Real | TableQMinUwtcFilt22 (from QLimitParameters) | 0 | |
| Real | TableQMinUwtcFilt31 (from QLimitParameters) | 0.8 | |
| Real | TableQMinUwtcFilt32 (from QLimitParameters) | -0.33 | |
| Real | TableQMinUwtcFilt41 (from QLimitParameters) | 1.2 | |
| Real | TableQMinUwtcFilt42 (from QLimitParameters) | -0.33 | |
| Real[:,:] | TableQMinUwtcFilt (from QLimitParameters) | [TableQMinUwtcFilt11, TableQMinUwtcFilt12; TableQMinUwtcFilt21, TableQMinUwtcFilt22; TableQMinUwtcFilt31, TableQMinUwtcFilt32; TableQMinUwtcFilt41, TableQMinUwtcFilt42] | Voltage dependency of reactive power minimum limit |
| Real | TableQMaxPwtcFilt11 (from QLimitParameters) | 0 | |
| Real | TableQMaxPwtcFilt12 (from QLimitParameters) | 0 | |
| Real | TableQMaxPwtcFilt21 (from QLimitParameters) | 0.001 | |
| Real | TableQMaxPwtcFilt22 (from QLimitParameters) | 0 | |
| Real | TableQMaxPwtcFilt31 (from QLimitParameters) | 0.3 | |
| Real | TableQMaxPwtcFilt32 (from QLimitParameters) | 0.33 | |
| Real | TableQMaxPwtcFilt41 (from QLimitParameters) | 1 | |
| Real | TableQMaxPwtcFilt42 (from QLimitParameters) | 0.33 | |
| Real[:,:] | TableQMaxPwtcFilt (from QLimitParameters) | [TableQMaxPwtcFilt11, TableQMaxPwtcFilt12; TableQMaxPwtcFilt21, TableQMaxPwtcFilt22; TableQMaxPwtcFilt31, TableQMaxPwtcFilt32; TableQMaxPwtcFilt41, TableQMaxPwtcFilt42] | Active power dependency of reactive power maximum limit |
| Real | TableQMinPwtcFilt11 (from QLimitParameters) | 0 | |
| Real | TableQMinPwtcFilt12 (from QLimitParameters) | 0 | |
| Real | TableQMinPwtcFilt21 (from QLimitParameters) | 0.001 | |
| Real | TableQMinPwtcFilt22 (from QLimitParameters) | 0 | |
| Real | TableQMinPwtcFilt31 (from QLimitParameters) | 0.3 | |
| Real | TableQMinPwtcFilt32 (from QLimitParameters) | -0.33 | |
| Real | TableQMinPwtcFilt41 (from QLimitParameters) | 1 | |
| Real | TableQMinPwtcFilt42 (from QLimitParameters) | -0.33 | |
| Real[:,:] | TableQMinPwtcFilt (from QLimitParameters) | [TableQMinPwtcFilt11, TableQMinPwtcFilt12; TableQMinPwtcFilt21, TableQMinPwtcFilt22; TableQMinPwtcFilt31, TableQMinPwtcFilt32; TableQMinPwtcFilt41, TableQMinPwtcFilt42] | Active power dependency of reactive power minimum limit |
| Electrical | |||
| Types.PerUnit | BesPu (from BaseWT4) | Shunt susceptance in pu (base UNom, SNom) | |
| Types.PerUnit | GesPu (from BaseWT4) | Shunt conductance in pu (base UNom, SNom) | |
| Types.PerUnit | ResPu (from BaseWT4) | Serial resistance in pu (base UNom, SNom) | |
| Types.PerUnit | XesPu (from BaseWT4) | Serial reactance in pu (base UNom, SNom) | |
| Control | |||
| Types.PerUnit | DipMaxPu (from BaseWT4) | Maximum active current ramp rate in pu/s (base UNom, SNom) (generator convention) | |
| Types.PerUnit | DiqMaxPu (from BaseWT4) | Maximum reactive current ramp rate in pu/s (base UNom, SNom) (generator convention) | |
| Types.PerUnit | DiqMinPu (from BaseWT4) | Minimum reactive current ramp rate in pu/s (base UNom, SNom) (generator convention) | |
| Types.PerUnit | Kipaw (from BaseWT4) | Anti-windup gain for active current in pu/s (base UNom, SNom) | |
| Types.PerUnit | Kiqaw (from BaseWT4) | Anti-windup gain for reactive current in pu/s (base UNom, SNom) | |
| Types.Time | tG (from BaseWT4) | Current generation time constant in s | |
| PLL | |||
| Types.Time | tPll (from BaseWT4) | PLL first order filter time constant in s | |
| Types.VoltageModulePu | UPll1Pu (from BaseWT4) | Voltage below which the angle of the voltage is filtered and possibly also frozen, in pu (base UNom) | |
| Types.VoltageModulePu | UPll2Pu (from BaseWT4) | Voltage below which the angle of the voltage is frozen, in pu (base UNom) (UPll2Pu < UPll1Pu typically) | |
| PControl | |||
| Types.PerUnit | Kpaw (from BaseWT4) | Anti-windup gain for active power in pu/s (base SNom) | |
| Types.PerUnit | DPMaxP4BPu | Maximum WT power ramp rate in pu/s (base SNom) (generator convention) | |
| Types.Time | tPAero | Aerodynamic power response time constant in s | |
| Types.Time | tPOrdP4B | Power order lag time constant in s | |
| Types.Time | tUFiltP4B | Filter time constant for voltage measurement in s | |
| CurrentLimiter | |||
| Types.CurrentModulePu | IMaxDipPu (from BaseWT4) | Maximum current during voltage dip at converter terminal in pu (base UNom, SNom) | |
| Types.CurrentModulePu | IMaxPu (from BaseWT4) | Maximum continuous current at converter terminal in pu (base UNom, SNom) | |
| Types.PerUnit | Kpqu (from BaseWT4) | Partial derivative of reactive current limit against voltage in pu (base UNom, SNom) | |
| Boolean | MdfsLim (from BaseWT4) | Limitation of type 3 stator current (false: total current limitation, true: stator current limitation) | |
| Boolean | Mqpri (from BaseWT4) | Prioritization of reactive power during FRT (false: active power priority, true: reactive power priority) | |
| Types.VoltageModulePu | UpquMaxPu (from BaseWT4) | WT voltage in the operation point where zero reactive power can be delivered, in pu (base UNom) | |
| Types.Time | tUFiltcl | Voltage filter time constant in s | |
| QControl | |||
| Types.PerUnit | IqH1Pu (from BaseWT4) | Maximum reactive current injection during dip in pu (base UNom, SNom) (generator convention) | |
| Types.PerUnit | IqMaxPu (from BaseWT4) | Maximum reactive current injection in pu (base UNom, SNom) (generator convention) | |
| Types.PerUnit | IqMinPu (from BaseWT4) | Minimum reactive current injection in pu (base UNom, SNom) (generator convention) | |
| Types.PerUnit | IqPostPu (from BaseWT4) | Post-fault reactive current injection in pu (base UNom, SNom) (generator convention) | |
| Types.PerUnit | Kiq (from BaseWT4) | Reactive power PI controller integration gain in pu/s (base UNom, SNom) | |
| Types.PerUnit | Kiu (from BaseWT4) | Voltage PI controller integration gain in pu/s (base UNom, SNom) | |
| Types.PerUnit | Kpq (from BaseWT4) | Reactive power PI controller proportional gain in pu (base UNom, SNom) | |
| Types.PerUnit | Kpu (from BaseWT4) | Voltage PI controller proportional gain in pu (base UNom, SNom) | |
| Types.PerUnit | Kqv (from BaseWT4) | Voltage scaling factor for FRT current in pu (base UNom, SNom) | |
| Integer | MqG (from BaseWT4) | General Q control mode (0-4): Voltage control (0), Reactive power control (1), Open loop reactive power control (2), Power factor control (3), Open loop power factor control (4) | |
| Types.PerUnit | RDropPu (from BaseWT4) | Resistive component of voltage drop impedance in pu (base UNom, SNom) | |
| Types.Time | tPost (from BaseWT4) | Length of time period where post-fault reactive power is injected, in s | |
| Types.Time | tQord (from BaseWT4) | Reactive power order lag time constant in s | |
| Types.VoltageModulePu | UMaxPu (from BaseWT4) | Maximum voltage in voltage PI controller integral term in pu (base UNom) | |
| Types.VoltageModulePu | UMinPu (from BaseWT4) | Minimum voltage in voltage PI controller integral term in pu (base UNom) | |
| Types.VoltageModulePu | UqDipPu (from BaseWT4) | Voltage threshold for UVRT detection in Q control in pu (base UNom) | |
| Types.VoltageModulePu | URef0Pu (from BaseWT4) | User-defined bias in voltage reference in pu (base UNom) | |
| Types.PerUnit | XDropPu (from BaseWT4) | Inductive component of voltage drop impedance in pu (base UNom, SNom) | |
| Integer | MqUvrt | UVRT Q control modes (0-2) (see Table 23, section 5.6.5.7, page 51 of the IEC norm N°61400-27-1:2015) | |
| Types.Time | tPFiltQ | Active power filter time constant in s | |
| Types.Time | tUFiltQ | Voltage filter time constant in s | |
| Types.VoltageModulePu | Udb1Pu | Voltage dead band lower limit in pu (base UNom) | |
| Types.VoltageModulePu | Udb2Pu | Voltage dead band upper limit in pu (base UNom) | |
| QLimiter | |||
| Boolean | QlConst (from BaseWT4) | True if limits are constant | |
| Types.ReactivePowerPu | QMaxPu (from BaseWT4) | Constant maximum reactive power at grid terminal in pu (base SNom) (generator convention) | |
| Types.ReactivePowerPu | QMinPu (from BaseWT4) | Constant minimum reactive power at grid terminal in pu (base SNom) (generator convention) | |
| Types.Time | tPFiltql | Filter time constant for active power measurement in s | |
| Types.Time | tUFiltql | Filter time constant for voltage measurement in s | |
| GridProtection | |||
| Types.PerUnit | fOverPu (from BaseWT4) | WT over frequency protection activation threshold in pu (base fNom) | |
| Types.PerUnit | fUnderPu (from BaseWT4) | WT under frequency protection activation threshold in pu (base fNom) | |
| Types.VoltageModulePu | UOverPu (from BaseWT4) | WT over voltage protection activation threshold in pu (base UNom) | |
| Types.VoltageModulePu | UUnderPu (from BaseWT4) | WT under voltage protection activation threshold in pu (base UNom) | |
| Initialization | |||
| Types.ComplexCurrentPu | i0Pu (from BaseWT4) | Initial complex current at grid terminal in pu (base UNom, SnRef) (receptor convention) | |
| Types.PerUnit | IGsIm0Pu (from BaseWT4) | Initial imaginary component of the current at converter terminal in pu (base UNom, SNom) (generator convention) | |
| Types.PerUnit | IGsRe0Pu (from BaseWT4) | Initial real component of the current at converter terminal in pu (base UNom, SNom) (generator convention) | |
| Types.PerUnit | IpMax0Pu (from BaseWT4) | Initial maximum active current at converter terminal in pu (base UNom, SNom) (generator convention) | |
| Types.PerUnit | IqMax0Pu (from BaseWT4) | Initial maximum reactive current at converter terminal in pu (base UNom, SNom) (generator convention) | |
| Types.PerUnit | IqMin0Pu (from BaseWT4) | Initial minimum reactive current at converter terminal in pu (base UNom, SNom) (generator convention) | |
| Types.ActivePowerPu | PAg0Pu (from BaseWT4) | Initial generator (air gap) power in pu (base SNom) (generator convention) | |
| Types.ReactivePowerPu | QMax0Pu (from BaseWT4) | Initial maximum reactive power at grid terminal in pu (base SNom) (generator convention) | |
| Types.ReactivePowerPu | QMin0Pu (from BaseWT4) | Initial minimum reactive power at grid terminal in pu (base SNom) (generator convention) | |
| Types.ComplexVoltagePu | u0Pu (from BaseWT4) | Initial complex voltage at grid terminal in pu (base UNom) | |
| Types.PerUnit | UGsIm0Pu (from BaseWT4) | Initial imaginary component of the voltage at converter terminal in pu (base UNom) | |
| Types.PerUnit | UGsRe0Pu (from BaseWT4) | Initial real component of the voltage at converter terminal in pu (base UNom) | |
| Operating point | |||
| Types.ActivePowerPu | P0Pu (from BaseWT4) | Initial active power at grid terminal in pu (base SnRef) (receptor convention) | |
| Types.ReactivePowerPu | Q0Pu (from BaseWT4) | Initial reactive power at grid terminal in pu (base SnRef) (receptor convention) | |
| Types.VoltageModulePu | U0Pu (from BaseWT4) | Initial voltage amplitude at grid terminal in pu (base UNom) | |
| Types.Angle | UPhase0 (from BaseWT4) | Initial voltage angle at grid terminal in rad | |
| Types.PerUnit | XWT0Pu (from BaseWT4) | Initial reactive power or voltage reference at grid terminal in pu (base SNom or UNom) (generator convention) | |
| UfMeasurement | |||
| Types.AngularVelocityPu | DfMaxPu | Maximum frequency ramp rate in pu/s (base omegaNom) | |
| Boolean | Mzc | Zero crossing measurement mode (true = 1 if the wind turbine protection system uses zero crossings to detect the frequency - otherwise false = 0) | |
| Types.Time | tfFilt | Filter time constant for frequency measurement in s | |
| Types.Time | tUFilt | Filter time constant for voltage measurement in s | |
| Types.Time | tphiFilt | Filter time constant for voltage angle measurement in s | |
| Mechanical | |||
| Types.PerUnit | CdrtPu | Drive train damping in pu (base SNom, omegaNom) | |
| Types.Time | Hgen | Generator inertia time constant in s | |
| Types.Time | Hwtr | WT rotor inertia time constant in s | |
| Types.PerUnit | KdrtPu | Drive train stiffness in pu (base SNom, omegaNom) | |
Connectors
| Type | Name | Default | Description |
|---|---|---|---|
| Dynawo.Connectors.ACPower | terminal (from BaseWT4) | Grid terminal, complex voltage and current in pu (base UNom, SnRef) (receptor convention) | |
| Modelica.Blocks.Interfaces.RealInput | omegaRefPu (from BaseWT4) | Reference frame for grid angular frequency in pu (base omegaNom) | |
| Modelica.Blocks.Interfaces.RealInput | PWTRefPu (from BaseWT4) | Active power reference at grid terminal in pu (base SNom) (generator convention) | |
| Modelica.Blocks.Interfaces.RealInput | tanPhi (from BaseWT4) | Tangent phi (can be figured as QPu / PPu) | |
| Modelica.Blocks.Interfaces.RealInput | xWTRefPu (from BaseWT4) | Reactive power loop reference : reactive power or voltage reference depending on the Q control mode (MqG), in pu (base SNom or UNom) (generator convention) |