This function computes the fan or pump efficiency for given normalized volume flow rate and performance data. The efficiency is
η = s(V̇/rN, d),
where η is the efficiency, rN is the normalized fan speed, V̇ is the volume flow rate, and d are performance data for fan or pump efficiency.
The function s(·, ·) is a cubic hermite spline. If the data d define a monotone decreasing sequence, then s(·, d) is a monotone decreasing function.
function efficiency extends Modelica.Icons.Function; input IBPSA.Fluid.Movers.BaseClasses.Characteristics.efficiencyParameters per "Efficiency performance data"; input Modelica.SIunits.VolumeFlowRate V_flow "Volumetric flow rate"; input Real d[:] "Derivatives at support points for spline interpolation"; input Real r_N(unit = "1") "Relative revolution, r_N=N/N_nominal"; input Real delta "Small value for switching implementation around zero rpm"; output Real eta(unit = "1", final quantity = "Efficiency") "Efficiency"; end efficiency;
min
attribute as otherwise numerical noise can cause
the assertion on the limit to fail.V_flow
instead of r_V
.
r_V/r_N
instead of r_V
to properly account for the
scaling law. See
#202
for a discussion and validation.