blockLimPID

P, PI, PD, and PID controller with limited output, anti-windup compensation, setpoint weighting and optional feed-forward

Extends from Modelica.Blocks.Interfaces.SVcontrol (Single-Variable continuous controller).

Information

Via parameter controllerType either P, PI, PD, or PID can be selected. If, e.g., PI is selected, all components belonging to the D-part are removed from the block (via conditional declarations). The example model Modelica.Blocks.Examples.PID_Controller demonstrates the usage of this controller. Several practical aspects of PID controller design are incorporated according to chapter 3 of the book:

Åström K.J., and Hägglund T.:
PID Controllers: Theory, Design, and Tuning. Instrument Society of America, 2nd edition, 1995.

Besides the additive proportional, integral and derivative part of this controller, the following features are present:

  • The output of this controller is limited. If the controller is in its limits, anti-windup compensation is activated to drive the integrator state to zero.
  • The high-frequency gain of the derivative part is limited to avoid excessive amplification of measurement noise.
  • Setpoint weighting is present, which allows to weight the setpoint in the proportional and the derivative part independently from the measurement. The controller will respond to load disturbances and measurement noise independently of this setting (parameters wp, wd). However, setpoint changes will depend on this setting. For example, it is useful to set the setpoint weight wd for the derivative part to zero, if steps may occur in the setpoint signal.
  • Optional feed-forward. It is possible to add a feed-forward signal. The feed-forward signal is added before limitation.

The parameters of the controller can be manually adjusted by performing simulations of the closed loop system (= controller + plant connected together) and using the following strategy:

  1. Set very large limits, e.g., yMax = Modelica.Constants.inf
  2. Select a P controller and manually enlarge parameter k (the total gain of the controller) until the closed-loop response cannot be improved any more.
  3. Select a PI controller and manually adjust parameters k and Ti (the time constant of the integrator). The first value of Ti can be selected, such that it is in the order of the time constant of the oscillations occurring with the P controller. If, e.g., vibrations in the order of T=10 ms occur in the previous step, start with Ti=0.01 s.
  4. If you want to make the reaction of the control loop faster (but probably less robust against disturbances and measurement noise) select a PID controller and manually adjust parameters k, Ti, Td (time constant of derivative block).
  5. Set the limits yMax and yMin according to your specification.
  6. Perform simulations such that the output of the PID controller goes in its limits. Tune Ni (Ni*Ti is the time constant of the anti-windup compensation) such that the input to the limiter block (= limiter.u) goes quickly enough back to its limits. If Ni is decreased, this happens faster. If Ni=infinity, the anti-windup compensation is switched off and the controller works bad.

Initialization

This block can be initialized in different ways controlled by parameter initType. The possible values of initType are defined in Modelica.Blocks.Types.Init.

Based on the setting of initType, the integrator (I) and derivative (D) blocks inside the PID controller are initialized according to the following table:

initType I.initType D.initType
NoInit NoInit NoInit
SteadyState SteadyState SteadyState
InitialState InitialState InitialState
InitialOutput
and initial equation: y = y_start
NoInit SteadyState

In many cases, the most useful initial condition is SteadyState because initial transients are then no longer present. If initType = Init.SteadyState, then in some cases difficulties might occur. The reason is the equation of the integrator:

der(y) = k*u;

The steady state equation "der(x)=0" leads to the condition that the input u to the integrator is zero. If the input u is already (directly or indirectly) defined by another initial condition, then the initialization problem is singular (has none or infinitely many solutions). This situation occurs often for mechanical systems, where, e.g., u = desiredSpeed - measuredSpeed and since speed is both a state and a derivative, it is natural to initialize it with zero. As sketched this is, however, not possible. The solution is to not initialize u_m or the variable that is used to compute u_m by an algebraic equation.

When initializing in steady-state, homotopy-based initialization can help the convergence of the solver, by using a simplified model a the beginning of the solution process. Different options are available.

  • homotopyType=Linear (default): the limitations are removed from the simplified model, making it linear. Use this if you know that the controller will not be saturated at steady state.
  • homotopyType=UpperLimit: if it is known a priori the controller will be stuck at the upper limit yMax, this option assumes y = yMax as a simplified model.
  • homotopyType=LowerLimit: if it is known a priori the controller will be stuck at the lower limit yMin, this option assumes y = yMin as a simplified model.
  • homotopyType=NoHomotopy: this option does not apply any simplification and keeps the limiter active throughout the homotopy transformation. Use this if it is unknown whether the controller is saturated or not at initialization and if the limitations on the output must be enforced throughout the entire homotopy transformation.

Parameters

TypeNameDefaultDescription
.Modelica.Blocks.Types.SimpleControllercontrollerType.Modelica.Blocks.Types.SimpleController.PIDType of controller
Realk1Gain of controller, must be non-zero
SI.TimeTi0.5Time constant of Integrator block
SI.TimeTd0.1Time constant of Derivative block
RealyMaxUpper limit of output
RealyMin-yMaxLower limit of output
Realwp1Set-point weight for Proportional block (0..1)
Realwd0Set-point weight for Derivative block (0..1)
RealNi0.9Ni*Ti is time constant of anti-windup compensation
RealNd10The higher Nd, the more ideal the derivative block
BooleanwithFeedForwardfalseUse feed-forward input?
RealkFF1Gain of feed-forward input
SI.TimeunitTime1
Initialization
InitinitTypeInit.InitialStateType of initialization (1: no init, 2: steady state, 3: initial state, 4: initial output)
Realxi_start0Initial or guess value for integrator output (= integrator state)
Realxd_start0Initial or guess value for state of derivative block
Realy_start0Initial value of output
Modelica.Blocks.Types.LimiterHomotopyhomotopyTypeModelica.Blocks.Types.LimiterHomotopy.LinearSimplified model for homotopy-based initialization
Advanced
Booleanstrictfalse= true, if strict limits with noEvent(..)

Connectors

TypeNameDefaultDescription
RealInputu_s (from SVcontrol)Connector of setpoint input signal
RealInputu_m (from SVcontrol)Connector of measurement input signal
RealOutputy (from SVcontrol)Connector of actuator output signal
Modelica.Blocks.Interfaces.RealInputu_ffOptional connector of feed-forward input signal

Components

TypeNameDefaultDescription
RealcontrolErroru_s - u_mControl error (set point - measurement)
Modelica.Blocks.Math.AddaddP
Modelica.Blocks.Math.AddaddD
Modelica.Blocks.Math.GainP
Modelica.Blocks.Continuous.IntegratorI
Modelica.Blocks.Continuous.DerivativeD
Modelica.Blocks.Math.GaingainPID
Modelica.Blocks.Math.Add3addPID
Modelica.Blocks.Math.Add3addI
Modelica.Blocks.Math.AddaddSat
Modelica.Blocks.Math.GaingainTrack
Modelica.Blocks.Nonlinear.Limiterlimiter
Modelica.Blocks.Sources.ConstantDzero
Modelica.Blocks.Sources.ConstantIzero
Modelica.Blocks.Sources.ConstantFFzero
Modelica.Blocks.Math.AddaddFF