modelSM_with_AVR_SD

Information

Generator model with automatic excitation control SD.

Модель синхронного генератора с подключенным АРВ сильного действия.

Parameters

TypeNameDefaultDescription
RealTgenOff1000Time of generator's disconnection, s
RealdTgenOff10Duration of generator's disconnection, s
RealPg100Active power, MW
RealUt20ARV voltage reference value, kV
RealPnom100Nominal maschine active power
RealUgnom20Nominal stator voltage, kV
RealSbaz1000Bazis power, MWA
RealXd_p1.869D-axis synchronous reactance, p.u.
RealXq_p1.869Q-axis synchronous reactance, p.u.
RealXs_p0.194Leakage reactance of stator winding, p.u.
RealTj_p7Inertia coefficient, s
RealX2q_p0.2337Q-axis subtransient reactance, p.u.
RealX2d_p0.2337D-axis subtransient reactance, p.u.
RealX1d_p0.3016D-axis transient reactance, p.u.
RealTd010D-axis transient time constant, s
RealT2d_p0.02D-axis subtransient time constant, s
RealT2q_p0.05Q-axis subtransient time constant, s
RealSigma0.0475Turbine statism coefficient, p.u.
RealTauC_up0.8Time constant of servo motor while valving control, s
RealTregOff50Turbine speed regulator off-time, s
RealTregOn1000Turbine speed regulator on-time, s
RealMtmax1.1Turbine overloading coefficient, p.u.
RealAimp1Fast turbine valving control amplitude, p.u.
RealMtmin0Turbine minimum-loading coefficient, p.u.
RealTimp1000Fast turbine valving control on-time, s
RealdTimp0.2Fast turbine valving control duration, s
RealTauC_down5Time constant of servo motor after valving control end, s
RealTkzOn1000HPP generators dropping on-time, s
RealPg_new100New power of HPP, MW
RealKemax2.0Multiplicity of forcing on, p.u.
RealKemin-0.6Multiplicity of forcing off, p.u.
RealK0u-10Voltage deviation control coefficient
RealK1u0Voltage derivative control coefficient
RealK0w0Frequency deviation control coefficient
RealK1if0Rotor current derivative control coefficient
RealK1w0Frequency derivative control coefficient
RealUforc0.85Voltage of field forcing input
RealUdeforc0.9Voltage of field forcing removing
RealTforcedelay0.1Delay of field forcing removing
RealDL00
RealTokp0.05The main channel of regulation time constant
Realcosfi_nom0.85Nominal maschine power coefficient, p.u.
Realn_gen1Number of generators
BooleandisplayPowerFlowtrueDisplay power flow
RealfbazG.sysData.fbazBazic frequency, Hz
Data.PQ_CapabilityTablepq_tableOMLET.Data.TVV_500_2
BooleaninServicetrueExcitation limiter condition

Connectors

TypeNameDefaultDescription
OMLET.Interfaces.Pin_v2inp

Components

TypeNameDefaultDescription
OMLET.Basic.Generators.SM_initialG
Excitation_systems.Regulators.AVR_SDAVR