modelSM_with_exciter_and_AVR_SD

Information

Generator model with automatic excitation (SD) control.

Модель синхронного генератора с подключенным АРВ сильного действия.

Parameters

TypeNameDefaultDescription
General
RealTgenOff1000Time of generator's disconnection, s
RealdTgenOff10Duration of generator's disconnection, s
RealTkzOn1000Generators dropping on-time, s
RealPg_new100New power of HPP, MW
Realn_gen1Number of generators
BooleandisplayPowerFlowtrueDisplay power flow
RealfbazG.sysData.fbazBazic frequency, Hz
BooleaninService_GtrueGenerator topological condition
Synchronous machine
RealPg100Active power, MW
RealUt20ARV voltage reference value, kV
RealPnom100Nominal maschine active power
RealUgnom20Nominal stator voltage, kV
RealSbaz1000Bazis power, MWA
RealXd_p1.869D-axis synchronous reactance, p.u.
RealXq_p1.869Q-axis synchronous reactance, p.u.
RealXs_p0.194Leakage reactance of stator winding, p.u.
RealX1d_p0.3016D-axis transient reactance, p.u.
RealX2q_p0.2337Q-axis subtransient reactance, p.u.
RealX2d_p0.2337D-axis subtransient reactance, p.u.
RealTj_p7Inertia coefficient, s
RealTd010D-axis transient time constant, s
RealT2d_p0.02D-axis subtransient time constant, s
RealT2q_p0.05Q-axis subtransient time constant, s
Realcosfi_nom0.85Nominal maschine power coefficient, p.u.
Data.PQ_CapabilityTablepq_tableOMLET.Data.TVV_500_2
RealKd0damping coefficient
Turbine
RealSigma0.0475Turbine statism coefficient, p.u.
RealTregOff50Turbine speed regulator off-time, s
RealMtmax1.1Turbine overloading coefficient, p.u.
RealMtmin0Turbine minimum-loading coefficient, p.u.
RealTauc0.15Slip deviation time constant
Exciter
RealKemax2.0Multiplicity of forcing on, p.u.
RealKemin-0.6Multiplicity of forcing off, p.u.
RealTe0.02Exciter time constant, s
BooleanselfExcitationtrueSign of self‑excitation (dependence on Ut)
RealKig_exc1.0
RealKif_exc1.0
RealKu_exc1.0
AVR
RealK0u-10Voltage deviation control coefficient
RealK1u0Voltage derivative control coefficient
RealK0w0Frequency deviation control coefficient
RealK1if0Rotor current derivative control coefficient
RealK1w0Frequency derivative control coefficient
RealDL00
RealTokp0.05The main channel of regulation time constant
BooleaninServicetrueReactive power limiter condition
RealUmax6AVR upper limit
RealUmin-6AVR lower limit
BooleaninService_1trueAVR_signal limiter condition
Forcing
RealUforc0.85Voltage of field forcing input
RealUdeforc0.9Voltage of field forcing removing
RealTforcedelay0.1Delay of field forcing removing

Connectors

TypeNameDefaultDescription
OMLET.Interfaces.Pin_v2inp

Components

TypeNameDefaultDescription
Excitation_systems.Regulators.AVR_SDAVR
Excitation_systems.Exciters.Exciterexciter
OMLET.Basic.Generators.SM_without_exciterG
Turbines.ASR_Regulator_ASR