modelLoadLimiterDU

GE General GGOV1DU Governor/Turbine Temperature Control

Information

The following documentation is adapted from [PSSE-Models], chapter 7.13:

Load limiter and temperature control system for the general purpose Turbine/Governor model GGOV1DU.

Parameters

TypeNameDefaultDescription
Types.PerUnitKturb1.5Turbine gain
Types.PerUnitKpload2Load limiter proportional gain for PI controller
Types.TimeAgingKiload0.67Load limiter integral gain for PI controller
Types.PerUnitDm0Mechanical damping coefficient
Types.PerUnitWfnl0.2No load fuel flow
Types.PerUnitVmax1Maximum valve position limit
Types.PerUnitVmin0.15Minimum valve position limit

Connectors

TypeNameDefaultDescription
Modelica.Blocks.Interfaces.RealOutputFSRTController Output
Modelica.Blocks.Interfaces.RealInputLDREFLoad Limiter reference value (pu)
Modelica.Blocks.Interfaces.RealInputTEXMMeasured Exhaust Temperature
Modelica.Blocks.Interfaces.RealInputPELECMachine electrical power (pu)

Components

TypeNameDefaultDescription
Modelica.Blocks.Math.GainKPLOAD
Modelica.Blocks.Continuous.Integrators6
Modelica.Blocks.Math.AddLoadlimiterPI
Modelica.Blocks.Math.Adddiff
Modelica.Blocks.Math.Gaingain
Modelica.Blocks.Nonlinear.LimitermaxLimiter
Modelica.Blocks.Math.Addtlim
Modelica.Blocks.Math.GainGain
Modelica.Blocks.Sources.Constantconst
Modelica.Blocks.Nonlinear.Limiterlimiter

Revisions

Reference

PSS®E Models

Last update

2020-11-22

Author

@maguilerac, @marcelofcastro

Contact

see UsersGuide.Contact