modelController

Controller for the solar plant

Information

Controller for DIgSILENT's implementation of the PV plant.

Parameters

TypeNameDefaultDescription
RealKp0.005Gain, Active Power PI-Controller
Types.TimeTip0.03Integration Time Constant, Active Power PI-Ctrl.
Types.TimeTr0.001Measurement Delay
Types.TimeTmpp5Time Delay MPP-Tracking
Types.PerUnitid_min0Min. Active Current Limit
Types.PerUnitid_max1Max. Active Current Limit
Types.VoltageU_min200Minimal allowed DC-voltage
Realiq_min-1Min. Reactive Current Limit
Realiq_max1Max. Reactive Current Limit
RealDeadband0.1Deadband for Dynamic AC Voltage Support
RealK_FRT2Gain for Dynamic AC Voltage Support
Booleani_EEGfalsefalse = acc. TC2007; true = acc. SDLWindV
Types.PerUnitmaxAbsCur1Max. allowed absolute current
Types.PerUnitmaxIq1Max.abs reactive current in normal operation
Types.PerUnituac01Initial voltage magnitude
Types.PerUnitiq0-0.2Initial q-axis current
Types.PerUnitid00.6Initial d-axis current

Connectors

TypeNameDefaultDescription
Modelica.Blocks.Interfaces.RealInputvdcref
Modelica.Blocks.Interfaces.RealInputuac
Modelica.Blocks.Interfaces.RealInputpred
Modelica.Blocks.Interfaces.RealInputvdcin
Modelica.Blocks.Interfaces.RealOutputid_ref
Modelica.Blocks.Interfaces.RealOutputiq_ref

Components

TypeNameDefaultDescription
Modelica.Blocks.Math.Feedbackfeedback
Modelica.Blocks.Continuous.FirstOrderMPP_delay
Modelica.Blocks.Continuous.FirstOrdervoltage_measurement_delay
Modelica.Blocks.Sources.Constantreference_voltage
Modelica.Blocks.Nonlinear.Limiterlimiter
Modelica.Blocks.Math.Feedbackfeedback1
Modelica.Blocks.Continuous.FirstOrderfilter
OpenIPSL.Electrical.Solar.PowerFactory.DIgSILENT.Auxiliary.ReactivePowerSupportreactivePowerSupport
OpenIPSL.Electrical.Solar.PowerFactory.DIgSILENT.CurrentLimitercurrent_limiter
OpenIPSL.Electrical.Solar.PowerFactory.DIgSILENT.Auxiliary.ActivePowerControlleractivePowerController

Revisions

Model Name

Current Controller

Reference

PowerFactory Implementation in Templates

Last update

January 2021

Author

@tinrabuzin

Contact

see UsersGuide.Contact

Model Verification

This model has not been verified against PowerFactory.