modelStaVmea

Voltage Measurement Device

Information

StaVmea model in PowerFactory measures voltage and frequency. The frequency in PowerFactory is computed with respect to the frame rotating with frequency equal to the synchronous machine. This is supported via the input omega here. Most of the OpenIPSL examples do not provide omega of the reference machine and thus, if the input is not connected the frequency is computed with respect to the 50 Hz reference frame and filtered to simulate the measurement delay.

Parameters

TypeNameDefaultDescription
Types.TimeTfe3/50Measurement delay
Types.Frequencyfn50Nominal frequency
Types.Angleangle_00Initial angle
Booleanuse_ref_machine_frequencyfalseUse reference machine frequency

Connectors

TypeNameDefaultDescription
OpenIPSL.Interfaces.PwPinp
Modelica.Blocks.Interfaces.RealOutputuVoltage magnitude [pu]
Modelica.Blocks.Interfaces.RealOutputfeElectrical frequency [Hz]
Modelica.Blocks.Interfaces.RealInputomegaReference machine frequency [Hz]

Components

TypeNameDefaultDescription
Realcosphi
Realsinphi
Types.FrequencydfFrequency difference
Types.PerUnitvxVoltage component
Types.PerUnitvyVoltage component

Revisions

Model Name

StaVmea

Reference

PowerFactory Manual

Last update

January 2021

Author

Tin Rabuzin, KTH Royal Institute of Technology

Contact

see UsersGuide.Contact

Model Verification

This model has not been verified against PowerFactory.

Description