| Integer | VARFLG | | 0 constant Q; 1 Reactive control; -1 Constant PF control |
| Integer | VLRFLG | | 0 Bypass V control; 1 WT3G1 Eqcmd limits;2 WT3G2 Eqcmd limits |
| Types.Time | Tfv | 0.15000 | Filter time constant in voltage regulator |
| Types.PerUnit | Kpv | 18.000 | Proportional gain in voltage regulator |
| Types.TimeAging | KIV | 5.0000 | Integrator gain in voltage regulator |
| Types.PerUnit | Xc | 0.0000 | Line drop compensation reactance |
| Types.Time | TFP | 0.50000E-01 | Filter time constant in torque regulator |
| Types.PerUnit | Kpp | 3.0000 | Proportional gain in torque regulator |
| Types.TimeAging | KIP | 0.60000 | Integrator gain in torque regulator |
| Types.PerUnit | PMX | 1.1200 | Max limit in torque regulator |
| Types.PerUnit | PMN | 0.10000 | Min limit in torque regulator |
| Types.PerUnit | QMX | 0.29600 | Max limit in voltage regulator |
| Types.PerUnit | QMN | -0.43600 | Min limit in voltage regulator |
| Types.PerUnit | IPMAX | 1.1000 | Max active current limit |
| Types.Time | TRV | 0.50000E-01 | Voltage sensor time constant |
| Types.PerUnit | RPMX | 0.45000 | Max power order derivative |
| Types.PerUnit | RPMN | -0.45000 | Min power order derivative |
| Types.Time | T_Power | 5.0000 | Power filter time constant |
| Types.PerUnit | Kqi | 0.50000E-01 | Mvar/Voltage gain |
| Types.PerUnit | VMINCL | 0.90000 | Min voltage limit |
| Types.PerUnit | VMAXCL | 1.2000 | Max voltage limit |
| Types.PerUnit | Kqv | 40.000 | Voltage/Mvar gain |
| Types.PerUnit | XIQmin | -0.50000 | |
| Types.PerUnit | XIQmax | 0.40000 | |
| Types.Time | Tv | 0.50000E-01 | Lag time constant in WindVar controller |
| Types.Time | Tp | 0.50000E-01 | Pelec filter in fast PF controller |
| Real | Fn | 1.0000 | A portion of online wind turbines |
| Types.PerUnit | wPmin | 0.69000 | Shaft speed at Pmin |
| Types.PerUnit | wP20 | 0.78000 | Shaft speed at 20% rated power |
| Types.PerUnit | wP40 | 0.98000 | Shaft speed at 40% rated power |
| Types.PerUnit | wP60 | 1.1200 | Shaft speed at 60% rated power |
| Types.PerUnit | Pmin | 0.74000 | Minimum power for operating at P100 speed |
| Types.PerUnit | wP100 | 1.2000 | Shaft speed at 100% rated power |
| Types.PerUnit | Vref | | Remote bus ref voltage |
| Types.PerUnit | v0 | | |
| Types.PerUnit | p0 | | |
| Types.PerUnit | q0 | | |