.PowerSystems.AC3ph.Lines

Transmission lines 3-phase

Information

Contains different types of transmission line models.
Faulted transmission lines contain a third terminal for connection to a fault-component.

The relations between line reactance (x,x0) and self- and mutual reactance (x_s,x_m) are

  x   = x_s - x_m,          reactance dq (stray reactance)
  x0  = x_s + 2*x_m,        reactance o (zero-component reactance)
  x_s =  (2*x + x0)/3       self reactance single conductor
  x_m = -(x - x0)/3         mutual reactance

Coupling:

  cpl = x_m/x_s >  0,        positive for lines

More info see package ACdq0Impedances.

Contents

NameDescription
RXline0RX line without length parameter, 3-phase dq0
RXlineRX transmission line, 3-phase dq0
PIlinePI transmission line, 3-phase dq0
TlineT transmission line, 3-phase dq0
FaultRXlineFaulted RX transmission line, 3-phase dq0
FaultTlineFaulted T transmission line, 3-phase dq0
PartialsPartial models
ParametersParameter data for interactive use