recordTrafoSat
Parameters for saturation transformer, 3-phase
Extends from TrafoMag (Parameters for magnetic coupling transformer, 3-phase).
Information
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Boolean | puUnits (from NominalDataTrafo) | true | = true, if scaled with nom. values (pu), else scaled with 1 (SI) |
| SI.Voltage | V_nom (from NominalDataTrafo) | {1, 1} | {prim,sec} nom Voltage (= base of pu) |
| SI.ApparentPower | S_nom (from NominalDataTrafo) | 1 | nominal Power (= base of pu) |
| SI.Frequency | f_nom (from NominalDataTrafo) | 50 | nominal frequency |
| Integer | tap_neutral (from TrafoIdeal) | {0, 0} | {1,2}: neutral tap position |
| SIpu.Voltage | dv_tap (from TrafoIdeal) | {0, 0} | {1,2}: delta-v per tap change |
| SIpu.Resistance | r_n (from TrafoIdeal) | {1, 1} | {1,2}: resistance neutral to grd (if Y) |
| SIpu.Resistance | r (from TrafoStray) | {0.05, 0.05} | {1,2}: resistance |
| SIpu.Reactance | x (from TrafoStray) | {0.05, 0.05} | {1,2}: stray reactance |
| SIpu.Reactance | x0 (from TrafoStray) | {x[1], x[2]} | {1,2}: stray reactance zero-comp |
| SIpu.Resistance | redc (from TrafoMag) | 500 | resistance eddy current |
| SIpu.Reactance | xm (from TrafoMag) | 500 | mutual reactance |
| SIpu.Reactance | xm0 (from TrafoMag) | 1 | mutual reactance zero |
| Real | psi_sat | 1.5 | saturation flux |
| SIpu.Reactance | xm_sat | 1 | mutual reactance saturated |