.SpotExamples.p_Precalculation.Z_matrixTrDat0

Information

Equivalent circuit on diagram layer!

Test generator, transient order = 1 (d-axis), = 0 (q-axis).

Transient data are:

  tc_d  = {0.684058354104098} d-axis
  to_d  = {4.171788659833010} d-axis
  xtr_d = {0.290231213872833} d-axis

Corresponding circuit data are:

  {r[1], r_0} = {0.0011, 0.005},      d-axis
  {r_0} = {0.005},                    q-axis
  {xsig_r[1], xsig_0} = {0.13, 0.17}, d-axis
  {xsig_0} = {0.17},                  q-axis
  {xm[1], xm_0} = {0, 1.6} d-axis (no coupling terms in transient order 1)
  {xm_0} = {1.6}           q-axis

The code uses

  xsig_s for xsig_0: armature leakage reactance
  xsig_r for xsig:   rotor leakage reactances
  r_s    for r_0:    armature (stator) resistance
  r_r    for r:      rotor resistances


Generated at 2024-12-21T19:25:56Z by OpenModelicaOpenModelica 1.24.3 using GenerateDoc.mos