Hypothesis and equations
Regarding the rolling shutters, the assumptions are :
fermeture_volet
< 95%), unchanged thermal resistanceWhen the window is open, the conductive heat transfer through the glass is not considered anymore, and instead of that an air renewal by natural ventilation is computed (refer to WindowNaturalVentilation
). In addition, the absence of glazing results in a suppression of direct and diffuse transmission factors.
Reduction coefficients of direct and diffuse fluxes may also be considered (useReduction=True
), based on :
FLUXsurfMask
)Concerning the calculation of natural lighting, the global and diffuse light transmission factors that must be filled correspond to TLW
, TLw_dif
, TLsw
and TLsw_dif
which are calculated precisely in the EN 410 norm. However, it is possible to find tabulated values in the document Valeurs tabulées des caractéristiques des parois vitrées et des correctifs associés aux baies (Tabulated values of glass walls features and patches associated with windows) from CSTB. Thus, by default :
TLW
= 0.5, TLW dif
= 0TLsw
= 0, TLsw_dif
= 0TLsw
= 0.09, TLsw_dif
= 0.03Bibliography
TF1 CLIM2000
CSTB. 2005. Guide réglementaire RT 2005. Règle d'application Th-Bât Th-U 3/5 Parois vitrées.
Natural lighting : Règles Th-L - Caractérisation du facteur de transmission lumineuse des parois du bâtiment - CSTB Mars 2012, Valeurs tabulées des parois vitrées - CSTB Mars 2012
Instructions for use
The thermal ports T_ext
and T_int
must be connected to temperature nodes (connect T_ext
to T_dry
of Meteofile
).
The external incident flows FLUX
can come from BoundaryConditions.Solar
models which are the link between walls and weather readers.
The internal incident flows FluxAbsInt
can come from occupants, heating systems but also from the redistribution of solar flux within a room (models from BoundaryConditions.Radiation
package).
Known limits / Use precautions
The following precautions should be considered:
k
represents the conductivity of the glazing without consideration of convective exchanges (different from Uglazing usually used).hs_ext
of convective transfer with outside default value is the value of the combined coefficient integrating LW convective and radiative exchanges.hs_ext
value must be changed - By default 16W / m².K can be taken since the radiative share is estimated to 5,13W / m².K outside, which corresponds to an environment temperature of 10 °CFor the calculation of illuminance, it is needed to clarify whether there are upstream masks because then the consideration of shadows caused by the architecture is done in the mask model.
Validations
BESTEST validation procedure
Validated model - Aurélie Kaemmerlen 12/2010
--------------------------------------------------------------
Licensed by EDF under a 3-clause BSD-license
Copyright © EDF 2009 - 2023
BuildSysPro version 3.6.0
Author : Aurélie KAEMMERLEN, EDF (2010)
--------------------------------------------------------------
Aurélie Kaemmerlen 02/2011 : Ajout du choix de considérer ou non des flux (GLO et CLO) sur la face interne via le booléen RadInterne
Aurélie Kaemmerlen 05/2011 :
Aurélie Kaemmerlen 06/2011 : Remplacement de la fonction PondTransDirect par un modèle plus complet possédant plusieurs formules de pondération du rayonnement direct. Il faudra l'étendre à l'absorption si besoin
Aurélie Kaemmerlen 10/2011 : Ajout des échanges avec l'environnement (ciel et sol)
Aurélie Kaemmerlen 10/2012 - Ajout d'une pondération linéaire en cosi
Frédéric Gastiger 03/2014 : ajout de la possibilité de commander un volet (fermeture_volet qui varie entre 0 et 1 - 1 quand le volet est fermé, 0 quand le volet est ouvert), avec la résistance thermique supplémentaire que cela engendre.
Amy Lindsay 03/2014 : - ajout de la possibilité d'ouvrir la fenêtre (true quand la fenêtre est ouverte, false quand elle est fermée) avec le débit de ventilation naturelle que cela engendre.
- ajout des coefficients de réduction des flux diffus/direct en fonction du type de fenêtre / porte fenêtre, de la présence de voilages, rideaux etc. issus des stages de Raphaelle Mrejen (2012) et Alexandre Hautefeuille (2013)
- changement des FluxSolInput en RealInput pour les flux absorbés intérieur pour éviter les confusions (ces flux absorbés en GLO ou en CLO peuvent non seulement provenir du soleil, mais aussi d'autres sources radiative)
Gilles Plessis 03/2014 : Simplification du modèle.
Amy Lindsay 04/2014 : Prise en compte du fait qu'avec la fenêtre ouverte, la part non vitrée de l'ouverture n'impose plus de facteurs de transmission du direct et du diffus.
Frédéric Gastiger 04/2015 : Correction d'une erreur dans le calcul du flux direct transmis à travers une fenêtre ouverte.
Laura Sudries, Vincent Magnaudeix 05/2015 : Prise en compte des flux lumineux incidents sur la baie pour calculer les flux lumineux transmis à travers la baie considérée (direct, diffus, réfléchi par le sol). Equations issues de la RT2012.
Benoît Charrier 01/2016 : Ajout de la prise en compte de l'absorption variable en fonction de l'angle d'incidence.