blockAirTemperatureMeasurementReturnFunctionality
Extends from BuildingControlLib.BuildingControl.VDI3813.Interfaces.Partial.PartialFunctionality (Superclass for all functionality blocks to provide graphics).
Information
Overview
Block that implements the functionality of "Air temperature measurement" from VDI 3813 [1, section 6.1.5, p. 13]. For semantic correctness it is specialized for return temperatures.
Functional Description
"The sensor functionAir temperature measurement (RA-FL section 2, column 4; informative function block Figure 6) is used to measure the air temperature of the room and, in air-bound heating and cooling systems, also the extract and supply air temperatures as well as the outdoor temperature. Room, supply or extract air temperatures are the input information for heating and cooling functions, whereas the outdoor temperature is required, e. g., for night-time cooling, summer compensation or for weather protection functions of the sunshade." [1, section 6.1.5, p. 13]
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Real | slope | 1 | Slope of temperature calibration curve |
| Real | yIntercept | 0 | Y-axis intercept of temperature calibration curve |
Connectors
| Type | Name | Default | Description |
|---|---|---|---|
| BuildingControlLib.BuildingControl.VDI3813.Interfaces.PhysicalRealInput | T | Physical signal of return air temperature measurement (expected unit is Kelvin). | |
| BuildingControlLib.BuildingControl.VDI3813.Interfaces.RealOutput | T_RETURN | Return air temperature of a ventilation system (expected unit is Kelvin). |
Revisions
- March 07, 2017 by Georg Ferdinand Schneider & Georg Ambrosius Peßler:
Implemented.