This is an AC/AC converter, based on a power balance between both circuit sides. The parameter conversionFactor defines the ratio between the RMS voltages as
V2 = conversionFactor V1
where V1 and V2 are the RMS voltages at the primary and secondary sides of the transformer, i.e., the connector N and P, respectively.
The loss of the converter is proportional to the power transmitted.
The parameter eta
is the efficiency of the transfer.
The loss is computed as
Ploss = (1-η) Ptr,
where Ptr is the power transmitted. The model is bi-directional and the power can flow from the primary to the secondary side and vice-versa. Furthermore, reactive power on both side are set to zero.
This model is derived from Modelica.Electrical.QuasiStatic.SinglePhase.Utilities.IdealACDCConverter.
replaceable
for the terminal.
stateSelect
statement to use
the current i[:]
on the connectors as iteration variable for the
initialization problem.