.BuildingSystems.Electrical.Transmission.Functions.R_AC_correction

Information

This function computes a correction factor for adapting the DC resistance when working with AC voltages. The correction factor assumes f = 60 Hz.

The correction is based on the type of cabel (AWG or kcmil) and the material.

Type (AWG or kcmil) Material Correction factor
1/0Aluminium1.0
2/0Aluminium1.001
3/0Aluminium1.001
4/0Aluminium1.001
250Aluminium1.002
300Aluminium1.003
350Aluminium1.004
400Aluminium1.005
500Aluminium1.007
600Aluminium1.010
700Aluminium1.013
750Aluminium1.015
800Aluminium1.017
1000Aluminium1.026
1250Aluminium1.040
1500Aluminium1.058
1750Aluminium1.079
2000Aluminium1.100
2500Aluminium1.142
Type (AWG or kcmil) Material Correction factor
1/0Copper1.0
2/0Copper1.001
3/0Copper1.002
4/0Copper1.004
250Copper1.005
300Copper1.006
350Copper1.009
400Copper1.011
500Copper1.018
600Copper1.025
700Copper1.034
750Copper1.039
800Copper1.044
1000Copper1.067
1250Copper1.102
1500Copper1.142
1750Copper1.185
2000Copper1.233
2500Copper1.326

Interface

function R_AC_correction
  input String size "Size of the commercial cable (AWG or kcmil)";
  input BuildingSystems.Electrical.Transmission.Types.Material material "Material of the cable";
  output Real correction "Correction factor";
end R_AC_correction;