.Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.FreezeProtection

Information

Freeze protection sequence for multizone AHU system. It is developed based on Section 5.16.12 of ASHRAE Guideline 36, May 2020.

  1. If the supply air temperature TAirSup drops below 4.4 °C (40 °F) for 5 minutes, send two (or more, as required to ensure that heating plant is active, minHotWatReq) heating hot-water plant requests, override the outdoor air damper to the minimum position, and modulate the heating coil to maintain a suppy air temperature of at least 6 °C (42 °F). Disable this function when supply air temperature rises above 7 °C (45 °F) for 5 minutes.
  2. If the supply air temperature TAirSup drops below 3.3 °C (38 °F) for 5 minutes, fully close both the economizer damper and the minimum outdoor air damper for 1 hour and set a Level 3 alarm noting that minimum ventilation was interrupted. After 1 hour, the unit shall resume minimum outdoor air ventilation and enter the previous stage of freeze protection.
  3. Upon signal from the freeze-stat (if installed), or if supply air temperature drops below 3.3 °C (38 °F) for 15 minutes or below 1 °C (34 °F) for 5 minutes, shut down supply and return (or relief) fan(s), close outdoor air damper, open the cooling-coil valve to 100%, and energize the CHW pump system. Also send two (or more, as required to ensure that heating plant is active, minHotWatReq) heating hot-water plant requests, modulate the heating coil to maintain the higher of the supply air temperature or the mixed air temperature at 27 °C (80 °F), and set a Level 2 alarm indicating the unit is shut down by freeze protection.

Revisions


Generated at 2024-11-23T19:25:52Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos