modelOutdoorAirFlow
Validate the sequences of setting AHU level minimum outdoor airflow rate
Information
This model shows how to compose the subsequences to find the minimum outdoor airflow setpoint of an AHU unit that serves three zones.
-
The block
zonToAhuwhich instantiates Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.Title24.SumZone, finds the sum and maximum of the zone level setpoints. -
The AHU level minimum outdoor airflow setpoint is then specified by block
ahu. See Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.Title24.AHU.
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.Title24.AHU | ahu | AHU level minimum outdoor airflow setpoint | |
| Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.Title24.SumZone | zonToAhu | From zone level to AHU level |
Revisions
-
March 14, 2022, by Jianjun Hu:
First implementation.