recordReformEIRChiller_Carrier_19XR_1259kW_6_26COP_Vanes

ReformEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes,  !- Name
    1258900,                 !- Reference Capacity {W}
    6.26,                    !- Reference COP {W/W}
    8.89,                    !- Reference Leaving Chilled Water Temperature {C}
    35.80,                   !- Reference Leaving Condenser Water Temperature {C}
    0.02593,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.03823,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.18,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.18,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-1258900
COP_nominal6.26
PLRMin0.18
PLRMinUnl0.18
PLRMax1.03
mEva_flow_nominal1000*0.02593
mCon_flow_nominal1000*0.03823
TEvaLvg_nominal273.15 + 8.89
TConLvg_nominal273.15 + 35.80
TEvaLvgMin273.15 + 7.22
TEvaLvgMax273.15 + 12.78
TConLvgMin273.15 + 22.61
TConLvgMax273.15 + 36.74
capFunT{1.013444E+00, -3.162384E-03, -4.418949E-03, 1.601141E-02, -1.029678E-03, 3.508932E-03}
EIRFunT{7.661241E-01, 1.157734E-02, -8.937094E-04, -6.824770E-03, 5.288283E-04, -7.378113E-04}
EIRFunPLR{4.602131E-02, 2.433945E-02, 6.394526E-05, -3.648563E-01, 1.854759E+00, -2.809346E-02, 0.000000E+00, -4.821515E-01, 0.000000E+00, 0.000000E+00}
etaMotor1.0