Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller Carrier 19XR 1801kW/6.34COP/VSD,  !- Name
    1800500,                 !- Reference Capacity {W}
    6.34,                    !- Reference COP {W/W}
    7.22,                    !- Reference Leaving Chilled Water Temperature {C}
    31.70,                   !- Reference Leaving Condenser Water Temperature {C}
    0.05161,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.06385,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller Carrier 19XR 1801kW/6.34COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller Carrier 19XR 1801kW/6.34COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller Carrier 19XR 1801kW/6.34COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Definition

record ReformEIRChiller_Carrier_19XR_1801kW_6_34COP_VSD = Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic(QEva_flow_nominal = -1800500, COP_nominal = 6.34, PLRMin = 0.20, PLRMinUnl = 0.20, PLRMax = 1.03, mEva_flow_nominal = 1000*0.05161, mCon_flow_nominal = 1000*0.06385, TEvaLvg_nominal = 273.15 + 7.22, TConLvg_nominal = 273.15 + 31.70, TEvaLvgMin = 273.15 + 6.67, TEvaLvgMax = 273.15 + 12.22, TConLvgMin = 273.15 + 19.63, TConLvgMax = 273.15 + 32.95, capFunT = {3.277256E-01, -9.423458E-02, -1.714249E-03, 7.496846E-02, -1.987466E-03, 4.807394E-03}, EIRFunT = {6.993760E-01, 3.436644E-03, 1.120695E-03, -3.794674E-03, 7.200808E-04, -1.623357E-03}, EIRFunPLR = {-3.986781E-03, 2.064845E-02, -1.459614E-05, -5.111204E-01, 2.257468E+00, -1.990453E-02, 0.000000E+00, -7.517775E-01, 0.000000E+00, 0.000000E+00}, etaMotor = 1.0);