.Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_19XR_897kW_7_23COP_VSD

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller Carrier 19XR 897kW/7.23COP/VSD,  !- Name
    896700,                  !- Reference Capacity {W}
    7.23,                    !- Reference COP {W/W}
    9.82,                    !- Reference Leaving Chilled Water Temperature {C}
    29.49,                   !- Reference Leaving Condenser Water Temperature {C}
    0.06782,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.0436,                  !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller Carrier 19XR 897kW/7.23COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller Carrier 19XR 897kW/7.23COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller Carrier 19XR 897kW/7.23COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Definition

record ReformEIRChiller_Carrier_19XR_897kW_7_23COP_VSD = Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic(QEva_flow_nominal = -896700, COP_nominal = 7.23, PLRMin = 0.20, PLRMinUnl = 0.20, PLRMax = 1.04, mEva_flow_nominal = 1000*0.06782, mCon_flow_nominal = 1000*0.0436, TEvaLvg_nominal = 273.15 + 9.82, TConLvg_nominal = 273.15 + 29.49, TEvaLvgMin = 273.15 + 5.56, TEvaLvgMax = 273.15 + 10.00, TConLvgMin = 273.15 + 18.72, TConLvgMax = 273.15 + 30.41, capFunT = {5.211989E-01, 7.968670E-02, -1.488365E-03, 1.974850E-02, -4.643458E-04, -7.786719E-04}, EIRFunT = {6.970381E-01, 5.701647E-02, -2.272629E-04, 8.496805E-03, 4.752264E-04, -2.759799E-03}, EIRFunPLR = {7.280764E-01, -5.949776E-02, 3.161338E-05, 8.871893E-01, -1.081399E+00, 5.804626E-02, 0.000000E+00, 4.825053E-01, 0.000000E+00, 0.000000E+00}, etaMotor = 1.0);