.Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_Carrier_23XL_724kW_6_04COP_Vanes

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller Carrier 23XL 724kW/6.04COP/Vanes,  !- Name
    724400,                  !- Reference Capacity {W}
    6.04,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    31.44,                   !- Reference Leaving Condenser Water Temperature {C}
    0.01779,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.01956,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller Carrier 23XL 724kW/6.04COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller Carrier 23XL 724kW/6.04COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller Carrier 23XL 724kW/6.04COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.19,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.19,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Definition

record ReformEIRChiller_Carrier_23XL_724kW_6_04COP_Vanes = Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic(QEva_flow_nominal = -724400, COP_nominal = 6.04, PLRMin = 0.19, PLRMinUnl = 0.19, PLRMax = 1.03, mEva_flow_nominal = 1000*0.01779, mCon_flow_nominal = 1000*0.01956, TEvaLvg_nominal = 273.15 + 5.56, TConLvg_nominal = 273.15 + 31.44, TEvaLvgMin = 273.15 + 5.56, TEvaLvgMax = 273.15 + 10.00, TConLvgMin = 273.15 + 22.12, TConLvgMax = 273.15 + 35.40, capFunT = {-1.116010E-01, -1.058351E-01, -1.829692E-03, 9.677921E-02, -2.169221E-03, 4.998660E-03}, EIRFunT = {5.899136E-01, 1.976846E-02, 8.755088E-04, -7.564222E-03, 8.775130E-04, -2.036856E-03}, EIRFunPLR = {3.645490E-01, 2.732140E-03, -5.356774E-05, 1.212025E-01, 5.491750E-01, 2.083941E-04, 0.000000E+00, -7.516191E-02, 0.000000E+00, 0.000000E+00}, etaMotor = 1.0);

Generated at 2024-04-28T18:16:21Z by OpenModelicaOpenModelica 1.22.3 using GenerateDoc.mos