Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller McQuay PEH 1104kW/8.00COP/Vanes,  !- Name
    1104200,                 !- Reference Capacity {W}
    8.00,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    22.59,                   !- Reference Leaving Condenser Water Temperature {C}
    0.02423,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.03028,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller McQuay PEH 1104kW/8.00COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller McQuay PEH 1104kW/8.00COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller McQuay PEH 1104kW/8.00COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.08,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.08,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Definition

record ReformEIRChiller_McQuay_PEH_1104kW_8_00COP_Vanes = Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic(QEva_flow_nominal = -1104200, COP_nominal = 8.00, PLRMin = 0.08, PLRMinUnl = 0.08, PLRMax = 1.03, mEva_flow_nominal = 1000*0.02423, mCon_flow_nominal = 1000*0.03028, TEvaLvg_nominal = 273.15 + 6.67, TConLvg_nominal = 273.15 + 22.59, TEvaLvgMin = 273.15 + 6.67, TEvaLvgMax = 273.15 + 12.22, TConLvgMin = 273.15 + 22.59, TConLvgMax = 273.15 + 34.29, capFunT = {7.757836E-01, 1.723720E-02, -2.761789E-03, 1.560171E-02, -1.133168E-03, 3.042701E-03}, EIRFunT = {7.355874E-01, -1.291195E-02, -1.168928E-03, 1.454443E-02, -4.975714E-06, 4.941841E-04}, EIRFunPLR = {2.216357E-01, 6.972382E-03, 5.022616E-05, -3.939145E-02, 9.582611E-01, -9.691500E-03, 0.000000E+00, -1.039758E-01, 0.000000E+00, 0.000000E+00}, etaMotor = 1.0);