.Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.ReformEIRChiller_McQuay_PFH_932kW_5_09COP_Vanes

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller McQuay PFH 932kW/5.09COP/Vanes,  !- Name
    931900,                  !- Reference Capacity {W}
    5.09,                    !- Reference COP {W/W}
    4.44,                    !- Reference Leaving Chilled Water Temperature {C}
    31.75,                   !- Reference Leaving Condenser Water Temperature {C}
    0.03785,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04732,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller McQuay PFH 932kW/5.09COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller McQuay PFH 932kW/5.09COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller McQuay PFH 932kW/5.09COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.09,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.09,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Definition

record ReformEIRChiller_McQuay_PFH_932kW_5_09COP_Vanes = Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic(QEva_flow_nominal = -931900, COP_nominal = 5.09, PLRMin = 0.09, PLRMinUnl = 0.09, PLRMax = 1.02, mEva_flow_nominal = 1000*0.03785, mCon_flow_nominal = 1000*0.04732, TEvaLvg_nominal = 273.15 + 4.44, TConLvg_nominal = 273.15 + 31.75, TEvaLvgMin = 273.15 + 3.33, TEvaLvgMax = 273.15 + 7.78, TConLvgMin = 273.15 + 19.66, TConLvgMax = 273.15 + 35.59, capFunT = {1.021236E+00, -1.680220E-03, -5.223075E-03, 2.922245E-02, -1.418909E-03, 4.211341E-03}, EIRFunT = {4.854031E-01, -1.891596E-02, -1.236212E-03, 1.975021E-02, -1.031869E-04, 6.964845E-04}, EIRFunPLR = {7.391619E-03, 9.094277E-03, -7.116487E-06, 1.699487E-01, 1.518580E+00, -8.713759E-03, 0.000000E+00, -7.007499E-01, 0.000000E+00, 0.000000E+00}, etaMotor = 1.0);