recordReformEIRChiller_Trane_CVHE_1125kW_4_89COP_Vanes
ReformEIRChiller Trane CVHE 1125kW/4.89COP/Vanes
A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
ReformEIRChiller Trane CVHE 1125kW/4.89COP/Vanes, !- Name
1125300, !- Reference Capacity {W}
4.89, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
36.27, !- Reference Leaving Condenser Water Temperature {C}
0.02776, !- Reference Chilled Water Flow Rate {m3/s}
0.02618, !- Reference Condenser Water Flow Rate {m3/s}
ReformEIRChiller Trane CVHE 1125kW/4.89COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ReformEIRChiller Trane CVHE 1125kW/4.89COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ReformEIRChiller Trane CVHE 1125kW/4.89COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode Type
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Attributes
| Name | Value |
|---|---|
| QEva_flow_nominal | -1125300 |
| COP_nominal | 4.89 |
| PLRMin | 0.10 |
| PLRMinUnl | 0.10 |
| PLRMax | 1.01 |
| mEva_flow_nominal | 1000*0.02776 |
| mCon_flow_nominal | 1000*0.02618 |
| TEvaLvg_nominal | 273.15 + 5.56 |
| TConLvg_nominal | 273.15 + 36.27 |
| TEvaLvgMin | 273.15 + 5.56 |
| TEvaLvgMax | 273.15 + 10.00 |
| TConLvgMin | 273.15 + 26.10 |
| TConLvgMax | 273.15 + 36.56 |
| capFunT | {3.738655E-01, -1.966419E-02, -1.212112E-03, 3.549468E-02, -5.800042E-04, 1.250514E-03} |
| EIRFunT | {4.744658E-01, -3.998991E-02, -8.170569E-05, 1.686296E-02, 8.315397E-05, 1.607491E-04} |
| EIRFunPLR | {3.526188E-01, -2.052741E-03, 5.127782E-06, -3.558764E-01, 1.168571E+00, 1.752891E-03, 0.000000E+00, -1.609826E-01, 0.000000E+00, 0.000000E+00} |
| etaMotor | 1.0 |