Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
ReformEIRChiller Trane CVHE 1329kW/5.38COP/Vanes, !- Name
1329300, !- Reference Capacity {W}
5.38, !- Reference COP {W/W}
6.11, !- Reference Leaving Chilled Water Temperature {C}
34.80, !- Reference Leaving Condenser Water Temperature {C}
0.04732, !- Reference Chilled Water Flow Rate {m3/s}
0.07098, !- Reference Condenser Water Flow Rate {m3/s}
ReformEIRChiller Trane CVHE 1329kW/5.38COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ReformEIRChiller Trane CVHE 1329kW/5.38COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ReformEIRChiller Trane CVHE 1329kW/5.38COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.29, !- Minimum Part Load Ratio
1.02, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.29, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode Type
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
record ReformEIRChiller_Trane_CVHE_1329kW_5_38COP_Vanes = Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic(QEva_flow_nominal = -1329300, COP_nominal = 5.38, PLRMin = 0.29, PLRMinUnl = 0.29, PLRMax = 1.02, mEva_flow_nominal = 1000*0.04732, mCon_flow_nominal = 1000*0.07098, TEvaLvg_nominal = 273.15 + 6.11, TConLvg_nominal = 273.15 + 34.80, TEvaLvgMin = 273.15 + 6.11, TEvaLvgMax = 273.15 + 10.00, TConLvgMin = 273.15 + 26.77, TConLvgMax = 273.15 + 41.98, capFunT = {2.971340E-01, 1.063097E-01, -4.449876E-03, 2.540435E-02, -5.696223E-04, 1.269921E-04}, EIRFunT = {9.460623E-01, 3.685465E-02, -7.530867E-04, -1.753701E-02, 5.832929E-04, -1.143458E-03}, EIRFunPLR = {-9.512023E-02, 8.704652E-03, -6.499682E-06, 1.336749E+00, -6.968012E-01, -8.318175E-03, 0.000000E+00, 4.497796E-01, 0.000000E+00, 0.000000E+00}, etaMotor = 1.0);