Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
ReformEIRChiller Trane CVHF 1758kW/6.87COP/Vanes, !- Name
1758300, !- Reference Capacity {W}
6.87, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
32.08, !- Reference Leaving Condenser Water Temperature {C}
0.06309, !- Reference Chilled Water Flow Rate {m3/s}
0.06309, !- Reference Condenser Water Flow Rate {m3/s}
ReformEIRChiller Trane CVHF 1758kW/6.87COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ReformEIRChiller Trane CVHF 1758kW/6.87COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ReformEIRChiller Trane CVHF 1758kW/6.87COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode Type
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
record ReformEIRChiller_Trane_CVHF_1758kW_6_87COP_Vanes = Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic(QEva_flow_nominal = -1758300, COP_nominal = 6.87, PLRMin = 0.20, PLRMinUnl = 0.20, PLRMax = 1.03, mEva_flow_nominal = 1000*0.06309, mCon_flow_nominal = 1000*0.06309, TEvaLvg_nominal = 273.15 + 5.56, TConLvg_nominal = 273.15 + 32.08, TEvaLvgMin = 273.15 + 5.56, TEvaLvgMax = 273.15 + 10.00, TConLvgMin = 273.15 + 20.44, TConLvgMax = 273.15 + 32.98, capFunT = {7.950124E-01, 3.170632E-02, -5.547610E-04, 4.268492E-03, -1.289046E-04, 4.509069E-04}, EIRFunT = {6.428117E-01, 1.299499E-02, 5.872739E-04, -5.532320E-03, 6.809308E-04, -1.480167E-03}, EIRFunPLR = {5.682807E-01, -3.888781E-02, 6.619097E-06, 1.715735E+00, -1.791541E+00, 3.851853E-02, 0.000000E+00, 5.124705E-01, 0.000000E+00, 0.000000E+00}, etaMotor = 1.0);