recordReformEIRChiller_York_YK_1881kW_6_53COP_Vanes

ReformEIRChiller York YK 1881kW/6.53COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller York YK 1881kW/6.53COP/Vanes,  !- Name
    1881400,                 !- Reference Capacity {W}
    6.53,                    !- Reference COP {W/W}
    8.89,                    !- Reference Leaving Chilled Water Temperature {C}
    31.65,                   !- Reference Leaving Condenser Water Temperature {C}
    0.04397,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.1041,                  !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller York YK 1881kW/6.53COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller York YK 1881kW/6.53COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller York YK 1881kW/6.53COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.19,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.19,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-1881400
COP_nominal6.53
PLRMin0.19
PLRMinUnl0.19
PLRMax1.03
mEva_flow_nominal1000*0.04397
mCon_flow_nominal1000*0.1041
TEvaLvg_nominal273.15 + 8.89
TConLvg_nominal273.15 + 31.65
TEvaLvgMin273.15 + 7.22
TEvaLvgMax273.15 + 12.78
TConLvgMin273.15 + 15.00
TConLvgMax273.15 + 32.45
capFunT{8.031671E-01, 3.618657E-02, -1.027472E-03, 1.237132E-02, -7.469842E-04, 1.123058E-03}
EIRFunT{4.262865E-01, 4.727402E-02, -1.347198E-03, 4.334960E-03, 5.282605E-04, -1.449676E-03}
EIRFunPLR{2.470999E-01, -4.530708E-03, 2.522038E-05, -5.464802E-01, 2.572647E+00, 3.398388E-03, 0.000000E+00, -1.261128E+00, 0.000000E+00, 0.000000E+00}
etaMotor1.0