recordReformEIRChiller_York_YK_4477kW_6_64COP_Vanes

ReformEIRChiller York YK 4477kW/6.64COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller York YK 4477kW/6.64COP/Vanes,  !- Name
    4476700,                 !- Reference Capacity {W}
    6.64,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    31.67,                   !- Reference Leaving Condenser Water Temperature {C}
    0.19558,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.24605,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller York YK 4477kW/6.64COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller York YK 4477kW/6.64COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller York YK 4477kW/6.64COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.41,                    !- Minimum Part Load Ratio
    1.06,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.41,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-4476700
COP_nominal6.64
PLRMin0.41
PLRMinUnl0.41
PLRMax1.06
mEva_flow_nominal1000*0.19558
mCon_flow_nominal1000*0.24605
TEvaLvg_nominal273.15 + 6.67
TConLvg_nominal273.15 + 31.67
TEvaLvgMin273.15 + 4.44
TEvaLvgMax273.15 + 7.78
TConLvgMin273.15 + 18.50
TConLvgMax273.15 + 31.67
capFunT{-5.612561E-01, -2.094117E-01, -8.555483E-03, 2.050690E-01, -6.451488E-03, 1.561052E-02}
EIRFunT{1.597687E-01, -3.513678E-02, -2.666547E-03, 5.561175E-02, -9.273482E-04, 1.559350E-03}
EIRFunPLR{6.263474E-01, -1.468760E-02, 2.187947E-04, -4.940077E-01, 1.448597E+00, 4.085582E-03, 0.000000E+00, -4.576722E-01, 0.000000E+00, 0.000000E+00}
etaMotor1.0