recordReformEIRChiller_York_YT_1758kW_6_28COP_Vanes

ReformEIRChiller York YT 1758kW/6.28COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller York YT 1758kW/6.28COP/Vanes,  !- Name
    1758300,                 !- Reference Capacity {W}
    6.28,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    34.60,                   !- Reference Leaving Condenser Water Temperature {C}
    0.07571,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09464,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller York YT 1758kW/6.28COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller York YT 1758kW/6.28COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller York YT 1758kW/6.28COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.06,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-1758300
COP_nominal6.28
PLRMin0.20
PLRMinUnl0.20
PLRMax1.06
mEva_flow_nominal1000*0.07571
mCon_flow_nominal1000*0.09464
TEvaLvg_nominal273.15 + 6.67
TConLvg_nominal273.15 + 34.60
TEvaLvgMin273.15 + 4.44
TEvaLvgMax273.15 + 8.89
TConLvgMin273.15 + 20.46
TConLvgMax273.15 + 39.72
capFunT{5.062633E-01, -9.373882E-03, -2.822764E-03, 4.202164E-02, -1.092132E-03, 2.074549E-03}
EIRFunT{5.699849E-01, -9.813327E-03, 4.223116E-04, 4.842283E-03, 4.078201E-04, -7.615896E-04}
EIRFunPLR{2.911331E-01, -4.317969E-03, 1.448369E-05, 6.226793E-01, 7.992053E-02, 3.393326E-03, 0.000000E+00, 1.919540E-02, 0.000000E+00, 0.000000E+00}
etaMotor1.0