modelAirRearDoorHexActive
Example model for air-cooled rack with active rear door heat exchanger
Extends from Buildings.Fluid.DataCenters.Racks.Hybrid.Examples.AirRearDoorHexPassive (Example model for air-cooled rack with passive rear door heat exchanger).
Information
Example model of an air-cooled IT rack with an active rear door heat exchanger.
This model is identical to Buildings.Fluid.DataCenters.Racks.Hybrid.Examples.AirRearDoorHexPassive except that the rear door heat exchanger has a built-in fan.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Units.SI.Power | PAir_nominal (from AirRearDoorHexPassive) | 48*1320 | Design power for air-cooled IT |
| Modelica.Units.SI.Temperature | TAirDatHal (from AirRearDoorHexPassive) | 303.15 | Air temperature in data hall |
| Modelica.Units.SI.SpecificHeatCapacity | cpAir_default (from AirRearDoorHexPassive) | MediumAir.specificHeatCapacityCp(MediumAir.setState_pTX(T = MediumAir.T_default, p = MediumAir.p_default, X = MediumAir.X_default[1:MediumAir.nXi])) | Specific heat capacity of air |
| Buildings.Fluid.DataCenters.Racks.Air.Data.Generic | datAir (from AirRearDoorHexPassive) | Air-cooled rack performance data | |
| Modelica.Units.SI.Temperature | TReaDooCooIn_nominal (from AirRearDoorHexPassive) | 273.15 + 25 | Rear door heat exchanger coolant supply temperature |
| Modelica.Units.SI.Temperature | TReaDooCooOut_nominal (from AirRearDoorHexPassive) | 273.15 + 35 | Rear door heat exchanger coolant return temperature |
| Modelica.Units.SI.Temperature | TAirReaDooIn_nominal (from AirRearDoorHexPassive) | TAirDatHal + (datAir.TOut_nominal - datAir.TIn_nominal) | Nominal air temperature entering the rear door heat exchanger |
| Modelica.Units.SI.MassFlowRate | mReaDoo_flow_nominal (from AirRearDoorHexPassive) | (PAir_nominal + datAir.PFan_nominal)/((TReaDooCooOut_nominal - TReaDooCooIn_nominal)*Buildings.Utilities.Psychrometrics.Constants.cpWatLiq) | Nominal mass flow rate for rear door heat exchanger at design conditions |
| Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Data.Passive.Generic | datReaDooHex (from AirRearDoorHexPassive) | ||
| Buildings.Fluid.DataCenters.Racks.Hybrid.Data.AirRearDoorHexPassive.Generic | dat (from AirRearDoorHexPassive) |
Components
Revisions
-
September 29, 2026, by Michael Wetter:
First implementation.