modelActive

Example model for an active rear door heat exchanger

Extends from Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Examples.BaseClasses.PartialExample (Partial example model for a rear door heat exchanger).

Information

Example model for an active rear door heat exchanger.

The model uses a constant water mass flow rate. The air mass flow rate is determined by the fan control. Because the IT load and the water mass flow rate are constant, the air mass flow rate is also constant after the initial transient.

Parameters

TypeNameDefaultDescription
Modelica.Units.SI.HeatFlowRateQ_flow_nominal (from PartialExample)-10000Nominal cooling duty (negative = heat removed from air)
Modelica.Units.SI.TemperatureTAirIn_nominal (from PartialExample)273.15 + 40Nominal air inlet temperature (warm server exhaust)
Modelica.Units.SI.TemperatureTAirOut_nominal (from PartialExample)273.15 + 30Nominal air outlet temperature of rear door heat exchanger
Modelica.Units.SI.TemperatureTCooIn_nominal (from PartialExample)273.15 + 20Nominal coolant inlet temperature
Modelica.Units.SI.TemperatureTCooOut_nominal (from PartialExample)273.15 + 30Nominal coolant outlet temperature
Modelica.Units.SI.MassFlowRatemAir_flow_nominal (from PartialExample)Q_flow_nominal/(TAirOut_nominal - TAirIn_nominal)/cpAir_defaultNominal air mass flow rate
Modelica.Units.SI.MassFlowRatemCoo_flow_nominal (from PartialExample)-Q_flow_nominal/(TCooOut_nominal - TCooIn_nominal)/cpCoo_defaultNominal coolant mass flow rate
Modelica.Units.SI.SpecificHeatCapacitycpAir_default (from PartialExample)MediumAir.specificHeatCapacityCp(MediumAir.setState_pTX(T = MediumAir.T_default, p = MediumAir.p_default, X = MediumAir.X_default[1:MediumAir.nXi]))Specific heat capacity of air
Modelica.Units.SI.SpecificHeatCapacitycpCoo_default (from PartialExample)MediumCoo.specificHeatCapacityCp(MediumCoo.setState_pTX(T = MediumCoo.T_default, p = MediumCoo.p_default, X = MediumCoo.X_default[1:MediumCoo.nXi]))Specific heat capacity of the coolant fluid
Modelica.Units.SI.PowerPIT_nominal10000Nominal IT load power handled by rear door heat exchanger
Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Data.Active.GenericdatPerformance data

Components

TypeNameDefaultDescription
Buildings.Fluid.Sources.Boundary_pTairSin (from PartialExample)Air pressure reference
Buildings.Fluid.Sources.MassFlowSource_TcooSou (from PartialExample)Coolant source at nominal conditions
Buildings.Fluid.Sources.Boundary_pTcooSin (from PartialExample)Coolant pressure reference
Buildings.Fluid.Sensors.TemperatureTwoPortsenTAirIn (from PartialExample)Air inlet temperature sensor
Buildings.Fluid.Sensors.TemperatureTwoPortsenTAirOut (from PartialExample)Air outlet temperature sensor
Buildings.Fluid.Sensors.TemperatureTwoPortsenTCooIn (from PartialExample)Coolant inlet temperature sensor
Buildings.Fluid.Sensors.TemperatureTwoPortsenTCooOut (from PartialExample)Coolant outlet temperature sensor
Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.ActivehexActive rear door heat exchanger
Sources.Boundary_pTairSouAir source at nominal conditions
FixedResistances.PressureDropresResistance of upstream rack

Revisions