modelPassive

Example model for a passive rear door heat exchanger

Extends from Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Examples.BaseClasses.PartialExample (Partial example model for a rear door heat exchanger).

Information

Example model for a passive rear door heat exchanger.

The model uses a constant air and water mass flow rate.

Parameters

TypeNameDefaultDescription
Modelica.Units.SI.HeatFlowRateQ_flow_nominal (from PartialExample)-10000Nominal cooling duty (negative = heat removed from air)
Modelica.Units.SI.TemperatureTAirIn_nominal (from PartialExample)273.15 + 40Nominal air inlet temperature (warm server exhaust)
Modelica.Units.SI.TemperatureTAirOut_nominal (from PartialExample)273.15 + 30Nominal air outlet temperature of rear door heat exchanger
Modelica.Units.SI.TemperatureTCooIn_nominal (from PartialExample)273.15 + 20Nominal coolant inlet temperature
Modelica.Units.SI.TemperatureTCooOut_nominal (from PartialExample)273.15 + 30Nominal coolant outlet temperature
Modelica.Units.SI.MassFlowRatemAir_flow_nominal (from PartialExample)Q_flow_nominal/(TAirOut_nominal - TAirIn_nominal)/cpAir_defaultNominal air mass flow rate
Modelica.Units.SI.MassFlowRatemCoo_flow_nominal (from PartialExample)-Q_flow_nominal/(TCooOut_nominal - TCooIn_nominal)/cpCoo_defaultNominal coolant mass flow rate
Modelica.Units.SI.SpecificHeatCapacitycpAir_default (from PartialExample)MediumAir.specificHeatCapacityCp(MediumAir.setState_pTX(T = MediumAir.T_default, p = MediumAir.p_default, X = MediumAir.X_default[1:MediumAir.nXi]))Specific heat capacity of air
Modelica.Units.SI.SpecificHeatCapacitycpCoo_default (from PartialExample)MediumCoo.specificHeatCapacityCp(MediumCoo.setState_pTX(T = MediumCoo.T_default, p = MediumCoo.p_default, X = MediumCoo.X_default[1:MediumCoo.nXi]))Specific heat capacity of the coolant fluid

Components

TypeNameDefaultDescription
Buildings.Fluid.Sources.Boundary_pTairSin (from PartialExample)Air pressure reference
Buildings.Fluid.Sources.MassFlowSource_TcooSou (from PartialExample)Coolant source at nominal conditions
Buildings.Fluid.Sources.Boundary_pTcooSin (from PartialExample)Coolant pressure reference
Buildings.Fluid.Sensors.TemperatureTwoPortsenTAirIn (from PartialExample)Air inlet temperature sensor
Buildings.Fluid.Sensors.TemperatureTwoPortsenTAirOut (from PartialExample)Air outlet temperature sensor
Buildings.Fluid.Sensors.TemperatureTwoPortsenTCooIn (from PartialExample)Coolant inlet temperature sensor
Buildings.Fluid.Sensors.TemperatureTwoPortsenTCooOut (from PartialExample)Coolant outlet temperature sensor
Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.PassivehexPassive rear door heat exchanger
Sources.MassFlowSource_TairSouAir source at nominal conditions