This model validates the model Buildings.Fluid.HeatExchangers.CoolingTowers.Merkel by comparing against results obtained from EnergyPlus.
The EnergyPlus results were obtained using the example file
CoolingTower:VariableSpeed
, with the cooling tower evaluated as
the CoolingTower:VariableSpeed:Merkel
model from EnergyPlus.
The difference in results of the cooling tower's leaving water temperature
(tow.TLvg
and TLvg.EP
)
during the middle and end of the simulation is because the mass flow rate is
zero. For zero mass flow rate, EnergyPlus assumes a steady state condition,
whereas the Modelica model is a dynamic model and hence the properties at the
outlet are equal to the state variables of the model.
Name | Description |
---|---|
MediumAir | Air medium model |
MediumWat | Water medium model |