This model illustrates the disturbance caused on the three-way
valve operation by an induced negative pressure differential at the
circuit boundaries. Two consumer circuits are connected to a
primary loop by means of
Buildings.Fluid.HydronicConfigurations.PassiveNetworks.SingleMixing.
The primary loop is configured with a flow resistance that
generates a negative pressure differential at the boundaries of the
consumer circuits (representing for instance a boiler with a high
pressure drop and no minimum flow requirement). Each consumer
circuit is equipped with a circulation pump that is sized to cover
the primary pressure differential. When the parameter
is_bal is false no bypass balancing valve
is considered. When this parameter is true a bypass
balancing valve is considered with the same design pressure drop as
the one in the primary loop. The pump design head remains unchanged
whatever the value of the parameter is_bal. The model
is configured in steady-state with open loop control. The load on
each consumer circuit is constant. The control valve of the first
circuit is modulated from fully open to fully closed position while
the control valve of the remote circuit is kept fully open.
When the bypass is not balanced, the flow reverses in the primary branch when the valve opening is below 20% which means that the load cannot be served any more.
When the bypass is balanced, no flow reversal occurs and the mixing function of the three-way valve is preserved over its whole opening range.
Note that the setting of this model represents an oversized control valve with a low authority β = 0.14. Setting a higher valve design pressure drop to reach an authority close to 0.5 alleviates the risk of primary flow reversal and reduces the need for a bypass balancing valve.