.Buildings.Fluid.Sensors.SensibleEnthalpyFlowRate

Information

This model outputs the sensible enthalphy flow rate of the medium in the flow between its fluid ports. In particular, if the total enthalpy flow rate is

tot = Ḣsen + Ḣlat,

where sen = ṁ (1-Xw) cp,air, then this sensor outputs Ḣ = Ḣsen.

If the parameter tau is non-zero, then the measured specific sensible enthalpy hout that is used to compute the sensible enthalpy flow rate sen = ṁ hout is computed using a first order differential equation. See Buildings.Fluid.Sensors.UsersGuide for an explanation.

For a sensor that measures tot, use Buildings.Fluid.Sensors.EnthalpyFlowRate.
For a sensor that measures lat, use Buildings.Fluid.Sensors.LatentEnthalpyFlowRate.

The sensor is ideal, i.e., it does not influence the fluid. The sensor can only be used with medium models that implement the function enthalpyOfNonCondensingGas(T).