modelStageChangeCommandPolyvalent
Validation model for stage change logic with polyvalent heat pumps
Extends from Buildings.Templates.Plants.Controls.StagingRotation.Validation.StageChangeCommand (Validation model for stage change logic).
Information
This model validates
Buildings.Templates.Plants.Controls.StagingRotation.StageChangeCommand
in a configuration with two reversible heat pumps and two polyvalent heat
pumps. In response to a varying flow rate, the variation of the required
capacity chaSta.capReq.y triggers stage change events. The
block
Buildings.Templates.Plants.Controls.Utilities.StageIndex is used to
illustrate how these events translate into a varying plant stage index
idxSta.y.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Integer | nSta (from StageChangeCommand) | chaSta.nSta | Number of stages |
| Integer | nEqu (from StageChangeCommand) | chaSta.nEqu | Number of pieces of equipment |
| Real | capHeaHp_nominal | 1E5 | Design heating capacity - Each heat pump (excluding polyvalent HP) |
| Real | capHeaPhp_nominal | 0.9E5 | Design heating capacity - Each polyvalent heat pump |
| Real | capHeaPhpShc_nominal | Buildings.Templates.Data.Defaults.COPHpWwHea/Buildings.Templates.Data.Defaults.COPHpAwHea*capHeaPhp_nominal | Design heating capacity in SHC mode - Each polyvalent heat pump |
| Configuration | |||
| Boolean | have_php (from StageChangeCommand) | false | Set to true for plants with polyvalent heat pumps |
| Real | cp_default (from StageChangeCommand) | 4184 | Default specific heat capacity |
| Real | rho_default (from StageChangeCommand) | 996 | Default specific heat capacity |
| Nominal condition | |||
| Real | capHea_nominal (from StageChangeCommand) | sum(chaSta.capEqu) | Installed heating capacity |
| Real | THeaWatSup_nominal (from StageChangeCommand) | 50 + 273.15 | Design HW supply temperature |
| Real | THeaWatRet_nominal (from StageChangeCommand) | 42 + 273.15 | Design HW return temperature |
| Real | VHeaWat_flow_nominal (from StageChangeCommand) | capHea_nominal/(THeaWatSup_nominal - THeaWatRet_nominal)/cp_default/rho_default | Design primary HW volume flow rate |
Components
Revisions
-
June 10, 2026, by Antoine Gautier:
First implementation.